SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: Sump Manufacturer Industry Standard X Professional Engineer <br /> Other(Specify) <br /> `fest Method Used: Pressure Vacuum X Hydrostatic <br /> _ Other(Spec) <br /> I'cst I-:�Iuipmcnt I.'sed: Caldwell Level Change Indicator Equipment Resolution_ .00? <br /> Sump# 1 Sump#2 Sump#3 Sump#4 <br /> Sump Diameter: 42" 42" 42" 42" <br /> Sump Depth: 40" 40" 40" 40" <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 11" 11" 10" 18" r <br /> Hi hest Piping Penetration: <br /> Height from Tank Top to Lowest 1219 8" 14" 14" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry Dry Dry <br /> Portion of Sump Tested' Water Level 28" Water Level 29 '/," Water Level 29" Water Level 29" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes Yes Yes <br /> roduct and water)?' <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe Yes Yes Yes Yes <br /> shutdown?` <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 9:0`1 9:55 10:00 9:10 <br /> Initial Reading(Rt): .001 .001 .001 .001 <br /> Test End Time: 9:35 10:25 10:30 9:40 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-Rt): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005130 Minutes .005/30 Minutes .005130 Minutes .005130 Minutes <br /> Test Result: X Pass Ll Fail X Pass ❑Fail X Pass ❑Fail X Pass 11 Fail <br /> Was sensor removed for testing? X Yes No INA X Yes '_1 No ❑NA X Yes C No `-INA X Yes '-'No NA <br /> Was sensor properly replaced and X Yes 'No NA X Yes No ❑NA X Yes - No 171 NA X Yes :No ! NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended allow-u or ailed tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to as of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />