Laserfiche WebLink
• 0 Page 11 of 11 <br /> 9. SPILL/OVERFII.L CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ®Other(Specify) 1 hour leak test <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> 0 Spill Box#87-1 Vapor Spill Box#87-2 Vapor Spill Box#91 Vapor Spill Box#Additive <br /> Vapor <br /> Bucket Diameter&Brand: 12" 12" 12" 12" <br /> Bucket Depth: 16" 13" 14.5" 14" <br /> Wait time between applying <br /> pressure/vacuum/water and 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> starting test: <br /> Test Start Time: 9:59am 9:59am 9:59am 9:59am <br /> Initial Reading(R,): 14%" 12%4" 14" 13'/4" <br /> Test End Time: 10:59am 10:59am 10:59am 10:59am <br /> Final Reading(RF): 14%" 121/49' 14" 13 '/d' <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-R,): 0 0 0 0 <br /> Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br /> Criteria: <br /> Test Result: ® Pass ❑Fail 1 ® Pass ❑Fail ® Pass ❑Fail ® Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 hour leak test conducted <br />