Laserfiche WebLink
9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ SEP <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑Profgssio� eer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: ancon TS-STS sump Test system Equipment Resolution: +/-0.002" <br /> Spill Box# 91 FB Spill Box#91 VB Spill Boa# Additive F Spill Box#Additive <br /> Bucket Diameter �12" <br /> 12„ 1211 12' <br /> Bucket Depth: 12" 14„ 14" <br /> Wait time between applying <br /> pressuretvacuumhvater and 30 minutes 30 minutes 30 minutes 30 minutes <br /> startin test: <br /> Test Stan Thne: 11:39 AM 11:39 AM 09:45 AM 09:45 AM <br /> Initial Reading(Rj): 1.2657 4.4565 3.495 2.5135 <br /> Test End Time: 11:54 AM 11:54 AM 10:01 AM 10:01 AM <br /> Final Reading(RF): 1.2642 4.4556 3.4941 2.8137 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> Change in Reading(RF-RI): -0.0015 -0.0007 -0.0009 0.0002 <br /> Pass/Fail Threshold or <br /> Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002" <br /> Test Result: Pass Pass Pass Pass <br /> Comments—(include information on repairs made prior to tesft and recwnmendedfolloiv up forfailed tests) <br />