Laserfiche WebLink
Betty Ho [EH] <br /> From: Debra Gehm <debra.gehm@fedex.com> <br /> Sent: Thursday, November 16, 2017 12:33 PM <br /> To: Betty Ho [EH] <br /> Cc: Kevin Eric McTee <br /> Subject: FXG Tracy 9-26-17 inspection Report Amendment Responses <br /> Importance: High <br /> Betty, <br /> I have addressed all but one of the listed violations from the 9-26-17 Amended UST Inspection Report. Please let me <br /> know if you have any questions or comments. <br /> Violation 105—Updated in CERS <br /> Violation 107—Updated in CERS <br /> Violation 305—Air pocket has been removed, and both ends of graduated cylinder have been capped. Brine level <br /> verified as appropriate height. <br /> Violation 306—UDC brine sensors have been moved to lowest point in dispensers#1, #2, #3,#5, and #7. <br /> Violation 313, 314, 316—Shear valve bolts were tightened, and piping union was also tightened. Absorbent pads and <br /> rags have been removed by Gettler-Ryan and space is dry. <br /> Violation 318—Diesel PLLD leak detector tested twice and passed.Tech suspects an air bubble in the line due to <br /> inactivity triggered original fail. <br /> Thank you, <br /> Deb <br /> Debra B. Gehm <br /> Senior Environmental Compliance Specialist <br /> FedEx Ground <br /> 1000 FedEx Drive <br /> Moon Township, PA 15108 <br /> 1.412.262.62.91 TEL RECEIVED <br /> 1.412.874.2977 CELL <br /> 1.412.859.2232 FAX <br /> fedex.comlus <br /> NOV 1 6 2011 <br /> ENVIRONMENTAL HEALTH <br /> IDEPARTMENT <br /> i <br />