Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #04932 <br /> Tank #: 1 Test Date: 2/ 4/97 <br /> Product: Unleaded Premium Work#: 340280 <br /> _ .. _ <br /> TANK TEST RESULT LEAK DETECTOR TEST RESULT <br /> Test Method: System 4000 Test Method: R.J. FTA <br /> Capacity: 12000 Manufacturer: Vaporless <br /> Diameter(in): 91 L/D Model: LD2000 <br /> Product Level(in): 64 L/D Serial#: 44475 <br /> Liquid Volume(Gals): 8400 Line Drain Back(ml): 100 <br /> Liquid Percent(%): 70.0% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 26 <br /> Coef. of Expansion: 0.000650 Metering Pressure(psi): 11 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.3 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 63 <br /> Head Pressure(psi): 1.7 r LINE TEST RESULT <br /> Test Start Time: 8:05:00 PM Test Method: TEI LT-3 <br /> Test End Time: 10:35:00 AM Pump Brand: Red Jacket <br /> Test Rate(gph): 0.023 <br /> System Type: Pressure <br /> Test Result: PASS <br /> Line Pressure(psi): 50 <br /> Line Start Time: 12:00:00 PM <br /> Test Method: ULLAGE Line End Time: 12:15:00 PM <br /> UllageVolume(gals.): 3600 <br /> Line Start Level: 260 <br /> Ullage Test Time: 11:00:00 AM Line End Level: 230 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.03 <br /> Ullage Result: PASS Line Test Result: PASS <br /> COMMENTS <br />