Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #04932 <br /> Tank #: 2 Test Date: 2/ 4/97 <br /> Product: Unleaded Plus Work#: 340280 <br /> TANK TEST RESULT LEAK DETECTOR TEST RESULT <br /> . � _ � <br /> Test Method: System 4000 Test Method: R.J. FTA <br /> Capacity: 12000 Manufacturer: Vaporless <br /> Diameter(in): 91 L/D Model: LD2000 <br /> Product Level(in): 65 L/D Serial#: 40528 <br /> Liquid Volume(Gals): 8600 Line Drain Back(ml): 80 <br /> Liquid Percent(%): 71.7% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 25 <br /> Coef. of Expansion: 0.000650 Metering Pressure(psi): 10 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 0.8 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 65 <br /> Head Pressure(psi): 1.8 <br /> Test Start Time: 8:05:00 AM Test Method: TEI LT-3 <br /> Test End Time: 10:35:00 AM Pump Brand: Red Jacket <br /> Test Rate(gph): 0.004 System Type: Pressure <br /> Test Result: PASS <br /> _ – — Line Pressure(psi): 50 <br /> "'-` LLAGE TEST RESULT Line Start Time: 12:20:00 PM <br /> Test Method: ULLAGE Line End Time: 12:35:00 PM <br /> UllageVolume(gals.): 3400 Line Start Level: 180 <br /> Ullage Test Time: 11:20:00 AM Line End Level: 160 <br /> Ullage Vacuum(psi): 1 Line Test Rate(gph): -0.02 <br /> Ullage Result: PASS <br /> Line Test Result: PASS <br /> COMMENTS <br /> 3 <br />