Ote Preparation and Installation Infuctions <br /> EMC Basic Monitoring Console <br /> cable runs greater than 50 feet are not warranted for 1. Measure the distance from the bottom of the tank to the <br /> proper operation. <br /> top of the probe riser pipe W. <br /> CAUTION:RS-232 CABLE RUNS LONGER THAN 2. Measure the distance from the bottom of the probe riser <br /> 50 FEET COULD RESULT IN DATA ERRORS,OR pipe to the top of the probe riser pipe (b). <br /> COMPONENT DAMAGE OR BOTH. <br /> 2. Peripheral Equipment Requirements. PROBE RiSEH PIPE <br /> Any peripheral equipment connected to an RS-232 TANK <br /> serial port must meet the following criteria: <br /> a. Peripheral equipment must be UL listed. .� <br /> b. The equipment must have an EIA standard RS-232C d <br /> or RS-232D communications protocol. A-d:c <br /> c. The equipment must NOT be installed over or in a <br /> hazardous location. <br /> SECTION 5. MAGNETOSTRICTfVE PROBE <br /> INSTALLATION Figure 12. Tank Diameter Measurement. <br /> M WARNING: TO PROTECT YOURSELF AND i <br /> OTHERS FROM BEING STRUCK BY VE- ' + LENGTM OF Pk0fJE . <br /> HICLES DURING WORK, BLOCK OFF YOUR Jai- `a' <br /> WORK AREA DURING INSTALLATION AND s 1 11 22 mi <br /> SERVICE. 5 `' 5.`"' <br /> 5'4" s 1 62 mi <br /> WARNING:TO AVOID ELECTRICAL SHOCK 6 " 83 m, <br /> WHICH COULD KILL YOU, BE SURE AC <br /> POWER TO THE MONITORING CONSOLE IS I 7 6 1 25 m. <br /> OFF DURING INSTALLATION. 6 (2 44 rni <br /> 25m <br /> 2.67 m <br /> ABOVEGROUND STORAGE TANK APPLICA. s 1s 74 <br /> TIONS:Installation Kit No.Q12856-984 is required 3 0 Rn <br /> for probe ma netostrictive be installation in 10 t3osm <br /> g p 106 (3 20 mi <br /> aboveground storage tanks. The kit includes: 11 (3 35 n)i <br /> 1-Adaptor, Part No. Q12598-31 <br /> 1- 5-foot length of 318" Flex Conduit, Part <br /> No. Q12598-32 Figure 13. Magnetostrictive Probe Dimensions <br /> 2 - 318" Straight Liquidtight Connectors, (Figure illustrates Magnetostrictive Probe <br /> Part No. Q12598-33 with 4" Floats) <br /> 1-Installation Manual,Part No.MDE2877 3. Subtract (b) from (a) to determine the correct tank <br /> WARNING:BE CAREFUL TO MAINTAIN diameter(c). <br /> YOUR BALANCE WHEN WORKING ON 4. Make sure the probe length(see Figure 13,"Magnetos- <br /> TOP OF THE STORAGE TANK. TANK trictive Probe Dimensions") is correct for the tank <br /> SURFACE IS VERY SLIPPERY. diameter. <br /> CAUTION:IT IS RECOMMENDED THAT B. RISER PIPE CAP PREPARATION. <br /> THE RISER PIPE BE A LIGHT COLOR The riser pipe cap must have a 3f8" tapped hole for <br /> TO REFLECT SUNLIGHT AND TO MAIN- passage of probe wires.Cap kits with pre-drilled hales for <br /> TAIN A REASONABLE 'TEMPERATURE. a standard 4"riser pipe are available from Gilbarco.Order <br /> PROBE MAY NOT FUNCTION PROP- Kit Number Q12598-05,one for each probe, <br /> ERLY IF .THE TEMPERATURE IN THE <br /> RISER IS ABOVE 700. If a kit has not been ordered, perform the following: <br /> NOTE:The Probe and Riser Cap and Ring Kit P/N I WARNING: DO NOT PERFORM DRILLING <br /> Q12598-05 is required for this installation. AND TAPPING PROCEDURES INA HAZARD- <br /> OUS AREA. DRILLING AND TAPPING CAN <br /> A.TANK DIAMETER MEASUREMENT'. CAUSE SPARKS AND IGNITE VOLATILE <br /> FUMES AND LIQUIDS FOUND IN A CLASS 1, <br /> Perform the following procedure to ensure that probes are GROUP D HAZARDOUS LOCATION.FAILURE <br /> installed in the proper tanks(see Figure 12,"Tank Diam- TO COMPLY COULD RESULT IN DEATH,SE- <br /> eter Measurement"). Inaccurate readings will result if RIOUS PERSONAL INJURY, PROPERTY' <br /> probes are not the correct length for the given tank t LOSS AND EQUIPMENT DAMAGE. <br /> diameter. <br /> 13 <br />