Laserfiche WebLink
LINE LEAK DETECTOR (LLD) TE <br />TEST DATE: December 17, 2015 <br />REPORT JAN 0 4 2016 <br />Al. FACILITY <br />Name Colonial Energy #40135 <br />Address 192 Lathrop Road, Lathrop, CA 95330 <br />Phone # 209-858-4998 <br />Contact Station Manager <br />A2. OWNER HEALTH ENVIRONMENT-At: <br />Name Colonial Energy, LLC. DEPARTMEN <br />Address 2860 N. Santiago Blvd. 2nd Floor, Orange, CA 92867 <br />Phone # 714-761-5426 <br />Contact Victor Hassan <br />A3. C U P A <br />Name San Joaquin County Environmental Health <br />Address 1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Notified 0 <br />Inspector Victoria McCarthney <br />Phone # 209-468-8257 <br />A4. TESTING CONTRACTOR <br />Name Walton Engineering, Inc. <br />Address P.O. Box 1025, W. Sacramento, CA 95691 <br />Lic # 617238 A, B, Haz <br />Contact Veronica Freitas <br />Phone# 916-373-1166 <br />I. LINE LEAK DETECTOR TEST RESULTS <br />_ _ Test Equipment Used: VapoHess VMl LDT-890 <br />Tank number <br />1 <br />3 <br />4 <br />Product contained <br />Gasoline -87-1 <br />Gasoline -91 <br />Dk+sel <br />Leak Detector Type <br />ELLD <br />_ <br />ELLD <br />ELLD <br />Leak detector make/model <br />08484000(11 <br />_ <br />0848480.OM <br />0848480.001 <br />Serial number <br />208852 <br />209154 <br />209150 <br />Functional Element Holding (psi) <br />19 <br />19 <br />19 <br />Resiliency (ml) <br />55 <br />65 <br />55 <br />Test leak rate (gph) <br />3.00 <br />3.00 <br />300 <br />Pump pressure (psi)31 <br />28 <br />31 <br />Metering pressure (psi) <br />0 <br />0 <br />0 <br />Pressure Restriction Reduction (psi) <br />31 <br />28 <br />91 <br />Length of Restriction Test (seconds) <br />0 <br />0 <br />0 <br />Full Flow Opening time (seconds) <br />0 <br />0 <br />g <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector makelmodel <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />Signature: 0 �" X WON <br />ENGINEERING, INC. <br />Technician: Jessie Wadkins / B35391 5307886 -UT Date: December 17 2015 <br />