L <br />2. The following continuous monitoring con- <br />ditions shall be compatible with the cavity <br />between the inner and outer tanks: <br />• Vented to atmosphere <br />• Vacuum — 5 psi maximum <br />• Positive air pressure (5 psi maximum) <br />• External hydrostatic pressure — 7 foot <br />maximum groundwater head pressure <br />over tank top. <br />3. Tanks 6' diameter and larger shall have an <br />integrally mounted reservoir' installed on the <br />tank for optional hydrostatic rrlonitoring. The <br />reservoir shall be constructed of fiberglass <br />reinforced plastic materials and warranted for <br />30 years against failure due to internal/exter- <br />nal corrosion and, when properly installed, <br />against structural failure (same as tank war- <br />ranty). <br />-Tanks 4' diameter DWT -6 Type II tanks do not include a fiber- <br />glass reservoir. A 4' diameter riser pipa screwed into the 4' <br />diameter annular space fitting,will serve as the resarvoPr. <br />4. Tank shall be designed with one 4" fitting <br />that will access the tank bottom between the <br />primary and secondary walls (annular space). <br />5. The double-wall tank monitor shall be <br />capable of detecting a breach in the inner <br />and/or outer tank under the following installed <br />conditions: <br />a. When the inner tank is empty. <br />b. When the inner tank is partially or com- <br />pletely full and the groundwater table is <br />below the tank bottom. <br />c. When the inner tank is partially or com- <br />pletely full and the tank is partially or <br />completely submerged in groundwater. <br />6. The leak detection performance of the <br />monitoring system shall be tested and verified <br />by a qualified independent consultant to <br />detect leaks as small as 0.10 gallons per hour <br />with a 99.9% probability of detection and less <br />than a 1.3% probability of a false alarm. <br />7. All monitoring equipment, 'including FRP <br />reservoirs and electronic controls, shall be <br />U.L. listed or accepted.. <br />8. If hydrostatically monitored, any solution <br />used in the tank annular space shall have <br />U.L. approval for compatibility with the tank <br />and be a contrasting color to the tank surface <br />to facilitate visual inspection of the tank for <br />leaks prior to burial. <br />2.02 Accessories <br />A. Anchor Straps — Provide glass fiber - <br />reinforced plastic anchor straps for each tank <br />shown. Number and location of straps shall <br />be as specified by manufacturer. Each strap <br />shall be capable of withstanding a maximum <br />load for each tank diameter as shown. <br />4'6— 4,200 lbs. <br />Go —18,000 lbs. <br />8'0 — 25,000 lbs. <br />10'6 — 32,000 lbs. <br />Straps shall be standard as supplied by the <br />tank manufacturer. <br />B. Certification Plate — <br />Underwriters Laboratory label shall be per- <br />manently affixed to each tank. <br />26 <br />F1 <br />L-A <br />C. Flanged Manways All control panels include: <br />1. The standard manway is 22" 1D. The 30" • Alarm lights for each circuit <br />and 36" la manways are optional. One 22" • Alarm test button <br />manway is provided with each tank. • Warning bell <br />2. All manways will be furnished complete • Transmission contacts for phone dialer <br />with U.L. fisted gaskets, bolts and covers. (not provided by Fluid Containment) <br />3. Location — see standard tank drawings. •,panel housing materials: fiberglass <br />4. For tanks 1,000 gallon capacity or less, the . Two spare light bulbs <br />steel manway cover shall have four 4" NPT . Wall mounting hardware <br />steel fittings. For tanks of 2,500 gallon (6' • Alarm bell silence switch <br />diameter) and 6,000 gallon (8' diameter) • ALPHA numeric display (tank inventory <br />capacity, the steel manway cover shall have gauge panel only). <br />five 4" NPT steel fittings welded in place. All . Fluid Containment electronics do not <br />other tanks will have the three 4" fittings weld- require shielded cable - <br />ed in place. • Tank gauge resolution ± 1132" <br />The 22" manway cover fittings are on an 8" Note: All wiring materials are provided by <br />radius from the center of the cover to the cen- the contractor. Wiring is required from the <br />ter line of the fitting. The 30" manway cover fit- power source to the control panel and from <br />tings are on a 12" radius; the 36" manway the control panel to the probe and sensor <br />cover fittings are on a 15" radius. assemblies. <br />5. Manway risers 48" in diameter and 42" 4. Switch Panel (Models SP -1 and SP -4 <br />high will be supplied to provide access to the for use with 550011 C4 and S13001 4C4 <br />manway lid. A 24" x 24" galvanized street box panels only) <br />with a cover must be provided by contractor The switch panel is preassembled and <br />for at grade installation. ready to wire. All electrical components are <br />6. Fiberglass manway extension tubes 24" U.L. listed NEMA 4 X. The electrical box is <br />long will be provided for the manways as out- non-metallic. <br />lined in Section 3 above. <br />D. FillTubes Features Model SPA Model SP -4 <br />Number at <br />Fill tubes of appropriate design will be sup- monitoring circuits 2 B <br />plied by contractor. Dimensions 8'12'H x 8'/2'Hx <br />E. Hydrostatic Monitor Accessories 31/=11V x 4D 91/2VV x 4D <br />1. Brine Antifreeze 5. Tank Gauge Probe (Model TGMP) <br />Brine solution Designation: BAS -30 The tank gauge probe is to be preassem- <br />Chemical Composition: 30%+calcium chloride, 1 % to 3% potassi- bled and ready to wire to the TGMS-02 con - <br />um chloride,/% to 2% sodium chloride, Balance water <br />Visual Appearance: Green in color, Cdorfess fluid trol panel. Probe lengths should be provided <br />Specific Gravity @ 60°F: 1.272.1.317 to match proper tank diameters. <br />Factory installed on tanks 20,000 gallon and under. Bull: brine job - <br />site installed on 25,000 gallon and 30,000 gallon tanks. F. Turbine Enclosures (Model TE Series) <br />2. Reservoir Sensor (Model RS10B & Model DF) The turbine enclosure is constructed of <br />Dimensions: fiberglass reinforced plastic. The turbine <br />Assembled Sensor, 2.38' dia. maximum x 1S'L 12'L maximum enclosure Is 42" or 48" in diameter and <br />Lead Cable PVC Riser Pipe <br />Cap & Fining: 4" dia. must be capable of mounting to the 42" or <br />Flexible Condug Switching: 318" dia. x 18'L 48" diameter secondary containment collar. <br />Contacts <br />RS10E: Titanium probes Buna-N float switch Turbine enclosures are a minimum of 2' in <br />DF: (2) Buna-N float switches length and are available in one -foot incre- <br />3. Electronic Control Panels ments to a maximum of five feet: <br />The control panel shall be constructed of U.L. <br />listed, electronic components. The control <br />panel power source is 120 volts A.C. (contrac- <br />tor provided wiring). The tank gauge probe <br />and sensor monitoring circuits are intrinsically <br />safe circuits, i.e., the circuit is incapable of <br />releasing sufficient electrical or thermal energy <br />to cause ignition of specific hazardous materi- <br />al under "normal" or "fault" operating condi- <br />tions. <br />Features <br />Model <br />Model <br />Model <br />sB0014C4 <br />S80011C4 <br />TGMS-02 <br />(Hydrostatic <br />iHydrostatic <br />{Tank Inventory <br />System only) <br />system only( <br />Gauge will Hydrostatic <br />System Capability) <br />Number of <br />monitoring <br />4 <br />1 <br />8 (2 probes & 6 <br />cimulls. <br />sensor circuits) <br />EledrIcA <br />Weatherproof <br />Weatherproof <br />Indoor <br />Components <br />{NEMA4XI <br />(NEMA4X) <br />(NEMA 1) <br />Rating <br />Dimensions <br />10'Hxl4'Wx8'D 10'Hx14'Wx8-D 10"Hx8-Wx3-118"0 <br />Total Power <br />02 amps <br />0.1 amps <br />0.1 amps <br />Consumption <br />20 watts <br />10 watts <br />10 watts <br />Monitoring <br />12 VNISA.C. <br />12 VaMs A.C. <br />11 Volts A.C. <br />Circuit Power <br />.003 amps <br />.003 amps <br />0002 amps <br />Inpul Power <br />120 VAC <br />120 VAC <br />120 VAC <br />Model No. Length <br />TE42-2 2' <br />TE42-3 3' <br />TE42-4 4' <br />TE42-5 5' <br />TE48-2 2' <br />TE48-3 3' <br />TE48.4 4' <br />TE48-5 5' <br />Cut lines for field trimming will be marked <br />on the top 12 inches of the turbine enclo- <br />sure in three inch increments. <br />The turbine enclosure top is constructed of <br />high-density polyethylene. The top diameter <br />is 42 inches. The lid openings are available <br />in various sizes: <br />Model No. Top Lid Opening Diameter <br />PT42-23 20.5 inches <br />PT42-27 24,5 inches <br />PT42-32 30.0 inches <br />The turbine enclosure top includes a fric- <br />tion -fit lid constructed of high-density poly- <br />ethylene. <br />r <br />