My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2011- 2015
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
N
>
99 (STATE ROUTE 99)
>
10878
>
2300 - Underground Storage Tank Program
>
PR0231598
>
COMPLIANCE INFO_2011- 2015
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/19/2024 1:51:12 PM
Creation date
11/5/2018 7:08:45 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2011- 2015
RECORD_ID
PR0231598
PE
2361
FACILITY_ID
FA0001146
FACILITY_NAME
MORADA CHEVRON FAST N EASY #60*
STREET_NUMBER
10878
Direction
N
STREET_NAME
STATE ROUTE 99
City
STOCKTON
Zip
95212
APN
08607002
CURRENT_STATUS
01
SITE_LOCATION
10878 N HWY 99 E
P_LOCATION
99
P_DISTRICT
004
QC Status
Approved
Scanner
SJGOV\rtan
Supplemental fields
FilePath
\MIGRATIONS\N\HWY 99\10878\PR0231598\COMPLIANCE INFO 2011- 2015 .PDF
QuestysFileName
COMPLIANCE INFO 2011- 2015
QuestysRecordDate
5/17/2017 4:55:05 PM
QuestysRecordID
3383937
QuestysRecordType
12
QuestysStateID
1
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
242
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
0 SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DEPARTMENT <br />1868 East Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.s ov.or lehd <br />CONTINUATION FORM Page: 4 of 5 <br />OFFICIAL INSPECTION REPORT Date: 03/28/13 <br />Facility Address: Morada Chevron, 10818 N Hwy 99, Stockton, CA Program: UST <br />SUMMARY OF VIOLATIONS <br />[CLASS 1. CLASS it. or MINOR -Notice to Comply] <br />204. The designated operator failed to check that the following alarms were responded to appropriately: <br />a. L2 - 89 STP 4-13-12 fuel alarm <br />b. L3 - 87 STP 4-21-12 fuel alarm <br />c. L1 - 91 STP 4-25-12 fuel alarm <br />During the monthly inspection, the designated operator shall review the alarm history for the previous <br />month, check that each alarm was documented and responded to appropriately, and attach a copy of <br />the alarm history with documentation taken in response to any alarms to the monthly report. Ensure that <br />designated operators performing monthly inspections at this facility are including all of the required <br />information on the reports. <br />204. The designated operator failed to check and note the correct test dates for the monitor system <br />certification and the secondary containment test on the past 12 months of designated operator monthly <br />inspection reports. The correct test dates are annual monitoring system certification = 1-27-12 and <br />triennial secondary containment test = 10-24-11. During the monthly inspection, the designated <br />operator shall check that all required testing and maintenance for the UST system have been completed <br />and document the dates they were done. Ensure that designated operators performing monthly <br />inspections at this facility are including all of the required information on the reports. <br />206. The designated operator employee training record was not found on site for training within the past <br />12 months. The designated operator shall train facility employees for which he or she is responsible in <br />the proper operation and maintenance of the UST system once every 12 months. The training shalt/ <br />include, but is not limited to: <br />1. Operation of the UST system in a manner consistent with the facility's best management practices <br />2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br />3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br />4. Name of the contact person(s) for emergencies and monitoring equipment alarms <br />Ensure that employees have been trained by the designated operator, maintain the list on site, and <br />submit a copy of the training records to the EHD by April 28, 2013. <br />ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT TIME AT EHD'S CURRENT HOURLY RATE. <br />P. -i -H RV. i I Title: <br />Garrett Backus (209) 468-2986 <br />EHD 23-02-003 Rev 04/19112 CONTINUATION FORM <br />
The URL can be used to link to this page
Your browser does not support the video tag.