M
<br />L
<br />K
<br />J
<br />H
<br />L
<br />F
<br />E
<br />F
<br />I
<br />ro
<br />0
<br />a
<br />a
<br />0
<br />M -
<br />m
<br />M
<br />1
<br />}
<br />TANK TESTING
<br />N
<br />9. PRE -INSTALLATION TEST SET UP: Prior to the pre-instaflation test, all shipping pads must
<br />MATERIALS: Double -Wall fiberglass reinforced plastic (FRP) storage tanks as supplied by Chevron
<br />be removed from the tank and the vacuum on the annular space must be released.
<br />d
<br />maximum diameter. Up to 39 of the particles may pass through a a8 sieve.
<br />A vacuum on the annular space is not a substitute for the pre -installation test. All installation
<br />m
<br />tests must be performed and recorded on company supplied forms.
<br />Double Wall Double Wall
<br />1 2
<br />1 3
<br />1 4 1
<br />5 i
<br />6
<br />H
<br />8
<br />9
<br />10
<br />n
<br />The pressure application system is to have two pressure gauges (range 0 to 10 psi with 5
<br />11000 11' - 7-1/8" Long it' - 6-1/8" Long -
<br />psi pressure reliefs) in the system, both in good condition and having been tested and
<br />CIL
<br />calibrated within a three-month period prior to the tank test (copy of the lest and
<br />fabric. Excess fabric at the top of the hole should be folded over the backfill material at
<br />calibration data to be furnished to the Company Representative upon request).
<br />z
<br />-
<br />,
<br />,
<br />A
<br />12_-. 1
<br />13 1
<br />6
<br />DO NOT install a tank which shows any evidence of leaking The Company Representative
<br />Other Contractor supplied equipment includes: vapor recovery (when specified) Phase 1 Assemblies:
<br />Is to be notified and will determine the course of action that will be followed.
<br />Z
<br />The Contractor is responsible for all labor, material and equipment necessary to conduct
<br />retractor, nozzle swivels, flow limiter, anti -kink springs, swivel stops, camps, extension,
<br />the following tests: ,
<br />Cul the submerged drop tube for product and heating fuel tanks at a 45' angle so the lowest point
<br />Pre -Installation Pressure Test, Air
<br />n:
<br />Post - Instollot ion Pressure Test, Air or Hydrostatic
<br />Z
<br />Z
<br />pollution rules. Orient the submerged drop tube to direct incoming product toward the opposite end
<br />I. ACCEPTABLE SOAPS: "Soaping" the tank exterior and fittings using a small garden -
<br />of the tank. Refer to installation drawings for additional details.
<br />type hand -pressurized spray unit. The test snap shall be a high foaming "soap" that
<br />bubbles easily If in contact with an air leak In the tank but won't bubble due to
<br />'C
<br />dispensing from the pressure applicator. Acceptable soaps ore:
<br />A crone or backhoe of sufficient lifting capacity must be used. The weight of the double wall
<br />(Y
<br />"Seam Test Concentrate:
<br />,
<br />" mwoy Loc High Soap
<br />n
<br />"7006 Southbend Leak Detector"
<br />equipment and lift by lifting lugs(s). On large tanks, greater than 8 diameter, use a spreader
<br />or approved equal
<br />bar to ensure a lift angle of at least 45 degrees at each lifting lug.
<br />-
<br />1
<br />}
<br />TANK TESTING
<br />07 APPROVED MATERIALS
<br />9. PRE -INSTALLATION TEST SET UP: Prior to the pre-instaflation test, all shipping pads must
<br />MATERIALS: Double -Wall fiberglass reinforced plastic (FRP) storage tanks as supplied by Chevron
<br />be removed from the tank and the vacuum on the annular space must be released.
<br />are to be installed by Contractor in accordance with the plans and speCiloolions.
<br />maximum diameter. Up to 39 of the particles may pass through a a8 sieve.
<br />A vacuum on the annular space is not a substitute for the pre -installation test. All installation
<br />2. STONE OR GRAVEL CRUSHINGS. Washed material, with particle size between 1/8" and
<br />".
<br />tests must be performed and recorded on company supplied forms.
<br />Double Wall Double Wall
<br />1 2
<br />1 3
<br />1 4 1
<br />5 i
<br />6
<br />1 7 I
<br />8
<br />9
<br />10
<br />n
<br />The pressure application system is to have two pressure gauges (range 0 to 10 psi with 5
<br />11000 11' - 7-1/8" Long it' - 6-1/8" Long -
<br />psi pressure reliefs) in the system, both in good condition and having been tested and
<br />4' - 5-1/8' O.D. e - 3-1/4" O.D.
<br />calibrated within a three-month period prior to the tank test (copy of the lest and
<br />fabric. Excess fabric at the top of the hole should be folded over the backfill material at
<br />calibration data to be furnished to the Company Representative upon request).
<br />(Note: O.D. is over the ribs)
<br />-
<br />,
<br />,
<br />the pressure prior to moving the tank or removing any of the fittings.
<br />12_-. 1
<br />13 1
<br />14
<br />04 DOUBLE WALL FRP TANK INSTALLATION
<br />TANK TESTING
<br />07 APPROVED MATERIALS
<br />9. PRE -INSTALLATION TEST SET UP: Prior to the pre-instaflation test, all shipping pads must
<br />MATERIALS: Double -Wall fiberglass reinforced plastic (FRP) storage tanks as supplied by Chevron
<br />be removed from the tank and the vacuum on the annular space must be released.
<br />are to be installed by Contractor in accordance with the plans and speCiloolions.
<br />maximum diameter. Up to 39 of the particles may pass through a a8 sieve.
<br />A vacuum on the annular space is not a substitute for the pre -installation test. All installation
<br />2. STONE OR GRAVEL CRUSHINGS. Washed material, with particle size between 1/8" and
<br />".
<br />tests must be performed and recorded on company supplied forms.
<br />Double Wall Double Wall
<br />Nominal Gallons ' Xerxes Owens/Cornino
<br />10, TANK TESTING - INSTRUCTIONS:
<br />" 12.000 37' - 0-1/2" Long 36'S' Long
<br />General: Notify Company Representative, who MUST observe all tests, at feast 24 hours
<br />8' - 0" O.D. 8' - 1-1/2" O.D.
<br />in advance of any test.
<br />10,000 31' - 6-1/2" Long 30' - 9i Long
<br />8' - 0" O.D. 8' - 1-1/2" O.D.
<br />The pressure application system is to have two pressure gauges (range 0 to 10 psi with 5
<br />11000 11' - 7-1/8" Long it' - 6-1/8" Long -
<br />psi pressure reliefs) in the system, both in good condition and having been tested and
<br />4' - 5-1/8' O.D. e - 3-1/4" O.D.
<br />calibrated within a three-month period prior to the tank test (copy of the lest and
<br />fabric. Excess fabric at the top of the hole should be folded over the backfill material at
<br />calibration data to be furnished to the Company Representative upon request).
<br />(Note: O.D. is over the ribs)
<br />-
<br />USE EXTREME CARE AROUND AND NEAR THE PRESSURIZED TANK. Relieve
<br />The contractor will furnish the exact hardware listed on the Bill of Malterials unless otherwise
<br />the pressure prior to moving the tank or removing any of the fittings.
<br />specified by the Company Rep.
<br />Hoechst Celanese Corp. - Trevira S1120
<br />DO NOT install a tank which shows any evidence of leaking The Company Representative
<br />Other Contractor supplied equipment includes: vapor recovery (when specified) Phase 1 Assemblies:
<br />Is to be notified and will determine the course of action that will be followed.
<br />Adapters, dust cops and nameplate holders. Phase II Equipment: Anti -Recirculation valve, high hose
<br />The Contractor is responsible for all labor, material and equipment necessary to conduct
<br />retractor, nozzle swivels, flow limiter, anti -kink springs, swivel stops, camps, extension,
<br />the following tests: ,
<br />Cul the submerged drop tube for product and heating fuel tanks at a 45' angle so the lowest point
<br />Pre -Installation Pressure Test, Air
<br />will be 3" minimum/4 maximum from the bottom of the tank. The highest point must be a
<br />Post - Instollot ion Pressure Test, Air or Hydrostatic
<br />maximum of 6" from the bottom of the tank. The 6" maximum dimension is critical due to air
<br />pollution rules. Orient the submerged drop tube to direct incoming product toward the opposite end
<br />I. ACCEPTABLE SOAPS: "Soaping" the tank exterior and fittings using a small garden -
<br />of the tank. Refer to installation drawings for additional details.
<br />type hand -pressurized spray unit. The test snap shall be a high foaming "soap" that
<br />bubbles easily If in contact with an air leak In the tank but won't bubble due to
<br />1. HANDLING: The Contractor is responsible for off-looding the tanks (from the delivery vehicle.
<br />dispensing from the pressure applicator. Acceptable soaps ore:
<br />A crone or backhoe of sufficient lifting capacity must be used. The weight of the double wall
<br />FRP tank is approximately 5000 - 6000 be.
<br />"Seam Test Concentrate:
<br />,
<br />" mwoy Loc High Soap
<br />2, LIFTING & MOVING: When lifting or moving an FRP tank, always use: Properly sized
<br />"7006 Southbend Leak Detector"
<br />equipment and lift by lifting lugs(s). On large tanks, greater than 8 diameter, use a spreader
<br />or approved equal
<br />bar to ensure a lift angle of at least 45 degrees at each lifting lug.
<br />-
<br />ii. PRE -INSTALLATION PRESSURE TEST, AIR: Use extreme care around and near
<br />Never roll or use cables or chains around an FRP tank. Set on smooth ground. free of rocks
<br />- any pressurized lank. Never pressurize secondary (outer) tank without pressurizing
<br />and foreign objects.
<br />the primary (inner) lank.
<br />Exception: FRP Tanks may be rolled up to 90 degrees on a 'smooth_ clegan surface when performing
<br />A.Primory (Inner) Tank Test: Locate a pressure gouge in the vent/monitor fitting
<br />the pre -installation" pressure lest.
<br />in the secondary (outer) tank, Locale o second pressure gouge at the fill opening
<br />-
<br />and connect the air pressure to this fitting.
<br />3. CHOCKING: Chock tanks in dccordance with manufacturer's recommendation until read for
<br />installation. If windy conditions exist or are expected, anchor tanks using minimum 12" nylon
<br />Pressurize the primary (inner) tank to a minimum of 4 psi (maximum 5 psi).
<br />or hemp rope over each tank and secure to stakes of adequate sHze to prevent movement of the
<br />Monitor the pressure gauges for 1 hour. 'I There should be no pressure increase
<br />tanks. -
<br />in the secondary (outer) tank. Soap all i,onk fittings.
<br />4. OPENINGS: All tanks ore shipped with dust covers in each opening). Dust covers are to remain
<br />B.Secondary (Outer) Tank Test: Leave the pressure on the primary lank. Using
<br />each opening until ready for the pre-inslallotion pressure test. All tanks must have either
<br />` o flexible air hose manifold, connect the r pressure hose from the primary tank
<br />air
<br />a dust cap in place or a 5 psi pressure relief valve in place at olll times.
<br />to the secondary tank. This manifold hose should be connected to the
<br />vent/monitor fitting that does not contain the air pressure gauge. Close the valve
<br />5. DAMAGE: Inspect oil conkscarefully for signs of damage upon receipt. Note any damage on the
<br />to the primarytank and disconnect the air supply. Pressurize the secondary tank
<br />shipping documents and notify the Company Rep. Contact the tonkk manufacturer.. for
<br />by opening the valve between the primary: and secondary tank. Soap the entire
<br />additional information. -
<br />tank and all fittings.
<br />If the tank is damaged at any other time, do not attempt repairs. Notify Company Rep. who
<br />Upon completion of the test, release pressure from the secondary tank prior to
<br />will determine the course of action.
<br />- releasing pressure from the primary tank.
<br />6. SETTING: Set tanks on prepared bed with a slope downward toward the fill end of the tank.
<br />iii. POST -INSTALLATION PRESSURE TESTS, AIR: Extreme care is to be used around
<br />A slope of 3" difference between the two extreme openings of the lank is desired. The
<br />and near any pressurized tank.
<br />acceptable range of slope is 4" maximum and 2' minimum; with the fill end lower than remote
<br />pump end of the tank. Tanks that exceed the acceptable slope or that slope downward to the
<br />A.Primary (Inner) Tank lest Perform this test with all tank risers and fillings
<br />remote pump end are improperly set and must be reset.
<br />attached. Tighten all tank fittings. Locale a pressure gauge in one of the annular
<br />space monitor fittings in the secondary (outer) lank. Locate a second pressure
<br />7. INSTALLATION WITH APPROVED MATERIALS: Place a 12" lift of backfiltl evenly around
<br />gauge with a 5 psi pressure relief, to one of the primary (inner) tank fittings and
<br />the tanks. Push backfill completely underneath the tank between the ribs and under the end
<br />connect the air pressure hose to this some lilting, Pressurize the primary (Inner)
<br />caps.. This is the most important port of the backfill process. Procedure can be done from
<br />tank to a minimum of 4 psi (maximum 5 psi), Soap all tank fittings and monitor
<br />bank or adjacent tank top. If a man will be in the hole to "work" the backfill,- hole must be
<br />the pressure gauges for a minimum of 1 hour. There should be no pressure
<br />shored or side sloped as prescribed by current OSHA regulations.
<br />increase in the secondary (outer) tonk. -
<br />Place second 12' lift or backfill evenly around the tanks. Again, repeat the "working" of
<br />B.Secondory (Outer) Tank Test: Disconnect the air supply but maintain the pressure
<br />backfill between the ribs. and under the end caps. Add backfill evenly around the tanks up
<br />on the primary took. Pressurize the secondary (outer) tank using a flexible air hose
<br />to the tops of the tanks.f
<br />manifold. Connect a pressure hose from the primary tank to the annular space
<br />monitor fitting that does not contain the air pressure gauge. Pressurize the
<br />Backfill to subgrade after piping and testing is completed.
<br />secondary tank by opening the manifold valve between the primary and secondary
<br />tank.
<br />B. INSTALLATION WITH ALTERNATE MATERIALS: All alternate materials must be compacted
<br />to 90% relative density (ASTM D-1557-70). Contractor is to furnish Compony Rep. with
<br />If necessary, bring pressure of both tanks to a minimum of 4 psi (maximum 5 psi)
<br />certification of compaction from a registered soil engineer.
<br />by reconnecting the air supply to the primary tank.
<br />Company Rep. is responsible for providing the exact installation specification for alternate
<br />Monitor the pressure for 1 hour and soap all tank fittings, risers and pipe
<br />materials.
<br />connections. Upon completion of the test, release the air pressure from the
<br />secondary tank prior to releasing pressure from the primory, tank. Damage to the
<br />primary tank may result if the pressure is not relieved from the secondary tank
<br />first
<br />'
<br />- Caution: Relieve all lank pressure prior to removing any fittings.
<br />No tank that shows any evidence of o leak Is to be kept in the system. Any
<br />damage incurred to the tank during, the installation will be the Contractor's
<br />'
<br />responsibility. The Company Rep. is to be notified of any damage and will
<br />determine the course of action to be followed-
<br />.
<br />If a hydrostatic test is required by the local agency, isolate the tank for testing and
<br />reconrfect when testing is complete. The hydrostatic test will be obtained by
<br />Chevron.
<br />11, INTERNAL MEASUREMENTS: Tnke internal diameter measurements at the fill and the remote
<br />pump openings, on both single and double Boll FRP tonks. The Contractor, witnessed by the
<br />Company Rep., is responsible for making and recording these measurements on a form provided
<br />-
<br />by the Company. Take the first set of measurements prior to placing any backfill around the
<br />Conk. The second set of measurements is token when the backfill has reached subgrade (prior
<br />to pouring the concrete slob),
<br />If the difference between any 2 sets of readings Is greater than 1-1/4", stop the job.
<br />Notify the Company Rep., who will determine the course of action. Contact the tank
<br />manufacturer for further guidance.
<br />-12. BALLASTING: Only the primary (inner) tank shall be used when ballasting the took. Never fill
<br />the secondary (outer) tank with a fluid. If the tanks ore ballasted, conduct a Hydrostatic Test
<br />(instead of the post -installation oir test) on the tank and fittings.
<br />13. BURIAL DEPTH: The burial depth from the top of the lank to ground level shall be o minimum
<br />-
<br />of 3 feet and a maximum of 7 feet. The fittings, if a monway is used, will be approximately
<br />5
<br />5 - 6 Inches off the top of the lank. This shall be considered for the slope of the piping and
<br />thus may affect the tank burial depth.
<br />14, VENTING: Vent the annular space between the primary and secondary tank only if required by
<br />local jurisdictions. Venting of the annular space is not required by the tank manufacturer. If
<br />required, manifold a 2 inch FRP pipe between the tanks and connected to a separate vent riser.
<br />Do not use the primary (product) tank vent to vent the annular space,
<br />-
<br />15. INTERSTITIAL MONITOR: A pull string may be In the tank, install a new pull string H the
<br />-
<br />string is missing, lost, or broken. The pull string is not o tank manufacturer warranty Item.
<br />Install the 'interstitial monitor at the bottom centerline of the FRP tank. Insert fish tope
<br />through the annular space. Tog both the pull string and probe signal cable at 12.5 fl. plus the
<br />burial depth. Attach the pull string to the probe and to the fish tape and pull probe into tank,
<br />When the tags on the signal cable and the pull string match, the probe is at the bottom
<br />centerline of the tank. The pull string is to remain in place and future accessible.
<br />15. INSTALLING THE CONTAINMENT SUMP: The containment sump must be watertight to
<br />-
<br />prevent liquid ingress or egress. Install a gasket between the tank collar and the containment
<br />sump and make a tight seal with a petroleum resistant butyl caulking.
<br />Test the containment sump with water if required by local inspectors or Company Rep,
<br />17. INSTALLING THE SPILL CONTAINMENT FILLBOX: The spill containment fillbox must be '
<br />-
<br />liquid light. Test all fillboxes by filling with .water for a minimum of 1 hour. There should
<br />"
<br />be no drop In the water level during this test. Do not drain water into the tank.
<br />2 3 4 5
<br />B 7 B 9
<br />0
<br />05 TANK HOLD—DOWN INSTALLATION
<br />GENERAL REQUIREMENTS: Anchor oil underground storage tanks with concrete hold-downs
<br />("logs" or deadmen") when specified by Company Rep, in the Scope of Work. Refer to drawing
<br />F-9 (N -PET -1`9P-1).
<br />Tank bedding, ballasting and lank hole backfill procedures are described under Section 02 of these
<br />specifications.
<br />The tank anchorage system shown on the drawings is designed for o maximum level of ground water
<br />equal to the subgrade level,
<br />MATERIALS:
<br />1, CONCRETE HOLD-DOWNS: Pre -cast, reinforced concrete "logs', 12" x 12" or 12' x 24" in
<br />cross-section, with chomfered edges. Length, as shown on the drawings. 1/2" diameter
<br />galvanized steel anchor loops are to be cost into logs" at locations shown. Pre -cast material
<br />shall have achieved its ultimate compressive strength of 2500 psi (28 days) prior to installation.
<br />Pre -cast concrete foundation piles which meet or exceed above specifications ore acceptable.
<br />2. WIRE ROPE CABLE: Hot -dip galvanized steel wire rope, minimum 1/2" diameter, breaking
<br />strength, 20.4K.
<br />3. HARDWARE: Cable clamps, cable guides, guards, etc. shall be hot -dip golvinized steel.
<br />4. PROTECTIVE COATING:' Prior to backfilling tonks, apply a generous quantity of "Chevron
<br />Asphalt Coating" by brush to all exposed steel cables, loops and hardware.
<br />INSTALLATION PROCEDURE:.
<br />1. Prepare the tank hole to receive hold-down "logs'. Install shoring (or side sloping) in
<br />accordance with Section 02,
<br />2. Pump the water out of the tank hole. Keep water out of the tank hole until tanks have
<br />been set, tied down. bollosted and backfllied.
<br />3. Insert each Coble through its own ranchor loop in the "log" reserving sufficient cable so that
<br />both ends of the cable will be kept at the lop of the tank hole after the logs" are set.
<br />Lower and position the 'logs' in the tank hole keeping both ends of the cables at the top
<br />of the hole. Install the 2' miniimum thick bedding material in tank hole. Smooth and
<br />slope per the tank bedding instructions.
<br />4. Proceed with setting the tanks by adding ballast as necessary to sink and keep down the
<br />tanks. Use only enough ballast fol hold the looks down until the backfill is even with the
<br />top of the tanks. (Refer to Section 04 for tank setting requirements.)
<br />Caution: Ballast level in tank must never exceed water (or backfill) level in lank hole
<br />- during installation.
<br />5. Install the cable guards, guides, ell , on the designated ribs of the took.
<br />(Note: "Designated Ribs" are marked by arrows on the lank surface.)
<br />Caution: Do not place straps or cables between the ribs of the tank.
<br />6. Pass each set of cables (a set of cables is those cables passing throughthe matching, or
<br />opposite, loops on -the logs) through the guides and loops as shown on the drawing.
<br />One end of each cable is be crossed over the top of the tank in theretainer portion of the
<br />hold-down strap. Using three cable clomps on each set of cables, clamp both cables
<br />together on top of the tank. Prior to tightening the clamps, tension the cables with "come-
<br />. a -longs" secured outside the lank hole. Use enough tension to lighten the cables but not
<br />to lift the logs" or crush the tank.
<br />Caution: All sets of cables on a tank must be tightened equally .to avoid tank deformation.
<br />The cable must rest on the top of the hold-down strop between the guides provided.
<br />Repeat this process for each set of tie -down cables.
<br />After all tie -downs are completed, commence the backfill procedures to the top of the
<br />tanks.
<br />B
<br />15
<br />T--]
<br />T7
<br />06 PATCH PAVING AND CONCRETE WORK
<br />M
<br />SCOPE OF WORK:
<br />Patch Paving: Patch paving work applies to minor work in connection with covering of pipe
<br />trenches, areas adjacent 4o tank slab and other areas disturbed during tank Installation.
<br />Concrete, Concrete work applies to installing tank slab, repair of drive slabs and other areas
<br />distributed during tank installation. Refer to applicable drawing F-3 of F-6
<br />for slab details.
<br />F
<br />E
<br />MARK DATE REVISIONS - INFNIL
<br />U.G. TANK AND PIPING
<br />INSTL, DBL WALL FRP TANKS
<br />9-2396
<br />25650 HWY 99 NO.,
<br />ACAMPO, CA.
<br />Chevron
<br />Northwest Region
<br />B
<br />ROBERT H. LEE & ASSOCIATES, INC.
<br />ARCHfTECTURE ENONEERVJO ENVRiONMEMVii SERVICEEI
<br />1137 NORTH MCGOWELL BOULEVARD PETALUMA CA. 94954 (707) 765-1660
<br />JOHN W. JOHNSON, ARCHITECT JAMES H. RAY, CML ENGINEER
<br />RHL REVIEW INIAL DATE DATE:
<br />PRELIMINARY
<br />PLANNING DR. BY:
<br />STEEL --BID
<br />BLDG PERMIT I APPR,:
<br />GENERAL BID P.
<br />PERMIT REV'S RHL. N $$44JIO
<br />CONSTRUCTION SHCE.
<br />Do nal use dluwing F^
<br />for
<br />coheir action
<br />unless Imitated
<br />10 11 12 13 14 16 16 17 18 -
<br />1
<br />1
<br />L
<br />07 APPROVED MATERIALS
<br />APPROVED.. BACKFILL MATERIALS:
<br />1. PEA GRAVEL: A clean, naturally rounded aggregate with a 1/8" minimum and a 3/4"
<br />maximum diameter. Up to 39 of the particles may pass through a a8 sieve.
<br />2. STONE OR GRAVEL CRUSHINGS. Washed material, with particle size between 1/8" and
<br />".
<br />1/2 Up to 3% of the particles may pass through a #8 sieve.
<br />Approved materials must be dry, free of ice and snow, and meet ASTM C-33, Para. 7.1 for quality
<br />K
<br />and soundness. The dry gravel density must be a minimum of 95 pounds per cubic foot.
<br />TANK HOLE LINER: Contractor is to provide a Filter Fabric Tank Hole Liner when:
<br />a) Tank hole is in unstable soil, or
<br />b) Specified by Company Rep. The entire tank hole (sides and bottom) shall be covered. Lay
<br />the fabric with 2 fool minimum overlaps.
<br />Bedding material, tie -down "logs" and sample wells ore to be placed on the top of the filter
<br />fabric. Excess fabric at the top of the hole should be folded over the backfill material at
<br />subgrade level.
<br />APPROVED FILTER FABRIC MATERIAL:
<br />J
<br />Reemay Inc. - Typar 3401 or Typor 3341
<br />Phillips Fibers Corp - Supac 4NP' Fabric
<br />Hoechst Celanese Corp. - Trevira S1120
<br />or fabric approved by the tank manufacturer,
<br />F
<br />E
<br />MARK DATE REVISIONS - INFNIL
<br />U.G. TANK AND PIPING
<br />INSTL, DBL WALL FRP TANKS
<br />9-2396
<br />25650 HWY 99 NO.,
<br />ACAMPO, CA.
<br />Chevron
<br />Northwest Region
<br />B
<br />ROBERT H. LEE & ASSOCIATES, INC.
<br />ARCHfTECTURE ENONEERVJO ENVRiONMEMVii SERVICEEI
<br />1137 NORTH MCGOWELL BOULEVARD PETALUMA CA. 94954 (707) 765-1660
<br />JOHN W. JOHNSON, ARCHITECT JAMES H. RAY, CML ENGINEER
<br />RHL REVIEW INIAL DATE DATE:
<br />PRELIMINARY
<br />PLANNING DR. BY:
<br />STEEL --BID
<br />BLDG PERMIT I APPR,:
<br />GENERAL BID P.
<br />PERMIT REV'S RHL. N $$44JIO
<br />CONSTRUCTION SHCE.
<br />Do nal use dluwing F^
<br />for
<br />coheir action
<br />unless Imitated
<br />10 11 12 13 14 16 16 17 18 -
<br />1
<br />1
<br />
|