Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32190 MARKET 4943 S.KINGSLEY(FRONTAGE RD STOCKTON CA.95206 <br /> Work Order#: 2222221 Date: 05/14/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ftA3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volumi Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ftA3) A/L Average Pass/Fail <br /> 7.511 49.00 9.2 2759.42 2760.55 1.130 1.13 <br /> 11 opw 27r PREMIUM 1.13 Pass <br /> 7.520 45.10 10.0 2760.55 2761.59 1.040 1.03 <br /> 9 opw 27r REG 1.03 Pass <br /> 7.513 <br /> 9 opw 27r PLUS 45.80 9.8 2761.59 1 2762.64 1.050 1.05 <br /> 1.05 Pass <br /> 7.516 <br /> 9 opw 27r PREMIUM 45.00 10.0 2762.64 2763.71 1.070 1.07 <br /> 1.07 Pass • <br /> 7.500 46.68 9.6 2763.71 2764.80 1.090 1.09 <br /> 10 opw 27r REG 1.09 Pass <br /> Type of System Tested: Gilbarco Vaaory <br />