Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32190 MARKET 4943 S.KINGSLEY FRONTAGE RD STOCKTON CA.95206 <br /> Work Order#: 2222221 Date: 05/14/2002 <br /> Technician: MICHAEL T LEVESOUE <br /> • <br /> Product Flow Rate Calculation Air Volume Metered (ftA3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Ftowrate Initial Final Volume Pressure Temp. Air Volum Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft-3) A/L Average Pass/Fail <br /> 7.520 47.15 9.6 2764.80 2765.86 1.060 1.05 <br /> 10 opw 27 PLUS 1.05 Pass <br /> 7.500 48.09 9.4 2765.86 2766.92 1.060 1.06 <br /> 10 opw 27r PREMIUM 1.06 Pass <br /> 7.496 52.35 8.6 2766.92 2767.91 0.990 0.99 <br /> 7 opw 27r REG 0.99 Incl <br /> 7.513 51.80 8.7 2767.91 2768.90 0.990 0.99 <br /> 7 opw 27r PLUS 0.99 Incl <br /> 7.504 52.20 8.6 2768.90 2769.89 0.990 0.99 <br /> 7 opw 27r PREMIUM 0.99 Incl <br /> Type of System Tested: Gilbarco Vapory <br />