Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32190 MARKET 4943 S.KINGSLEY(FRONTAGE RD) STOCKTON CA.95206 <br /> Work Order#: 2222221 Date: 05/14/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ft^3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volum Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft^3) A/L Average Pass/Fail <br /> 7.504 48.44 9.3 2775.18 2776.27 1.090 1.09 <br /> 8 opw 27r PREMIUM <br /> 1.09 Pass <br /> 7.521 46.72 9.7 2776.27 2777.34 1.070 1.06 <br /> 6 opw 27r REG <br /> 1.06 Pass <br /> 7.503 47.50 9.5 2777.34 2778.43 1.090 1.09 <br /> 6 opw 27r PLUS <br /> 1.09 Pass <br /> 7.498 48.22 9.3 2778.43 2779.55 1.120 1.12 <br /> 6 opw 27r PREMIUM <br /> 1.12 Pass <br /> 7.514 48.15 9.4 2779.55 2780.63 1.080 1.08 <br /> 5 opw 27r REG <br /> 1.08 Pass <br /> Type of System Tested: Gilbarco Vapory <br />