Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32190 MARKET 4943 S.KINGSLEY FRONTAGE RD STOCKTON CA.95206 <br /> Work Order#: 2222221 Date: 05/14/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ft^3) Ambient Conditions Corrected <br /> Gallons 'sFinal <br /> (g) Times Flowra[e =InitiialgFinal Volume Pressure Temp. Air Volum Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Metered Inches Hg Degrees F (f[^3) A/L Average Pass/Fail <br /> 4 opw 27r REG 7.510 1 48.71 9.3 2785.88 2786.00 1 0.120 0.12 <br /> 0.12 Pass <br /> 7.526 49.00 9.2 2786.00 2787.12 1 1.120 1.11 <br /> 4 opw 27r PLUS <br /> 1.11 Pass <br /> 4 opw 27r PREMIUM 7.505 47.50 1 9.5 2787.12 1 2788.25 1 1.130 1.13 <br /> 1.13 Pass <br /> 2 opw 27r REG 7.507 54.47 8.3 2788.25 2789.29 1.040 1.04 <br /> 1.04 Pass • <br /> 2 opw 27r PLUS 7.491 53.90 8.3 2789.29 2790.31 1.020 1.02 <br /> 1.02 Pass <br /> Type of System Tested: Gilbarco Vapory <br />