Laserfiche WebLink
SWRCB,January 2002 Page 5 of 5 <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Other(Spccify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> Fill Sump#Fill Fill Sump#Middle Fill Sump# Fill Sump# <br /> UE042UODI UE042U001 <br /> Sump Diameter: 38" 38" <br /> Surnp Depth: 40.5" 41" <br /> Height from Tank Top to Top of 10" N/A <br /> High tPipink Penetration: <br /> Height from Tank Top to Lowest 8" 14" <br /> Electrical Penetration: <br /> Condition of sum prior to testing: Good Good <br /> Portion of Sump Tested: 2"above an 2"above Collar <br /> Sumv Material: Fiberglass Fiberglass <br /> Wait time between applying 15 min 15 min <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 12:02 pm 12:18 yrn 12:02 pm 12:18 pm <br /> Initial Reading Ri): 2.2099 2.2100 1.3296 1.3291 <br /> Test End Time: 12:17 prn 12:33 pm 12:17 pm 12:33 pm <br /> Final Reading[90.: 2.2099 2.2099 1.3291 1.3286 <br /> "fest Duration: 15 min 15 min 15 min 15 min <br /> Chan a in Reading Rf-Ri : .0000 .0001 .0005 .0005 <br /> Pass/Fail Threshold or Criteria: 002 .002 <br /> Test Result: 0 Pass © Fail 0 Pass ❑ Fail ❑ Pass ❑ Fall ❑ Pass Cl Fall <br /> Is there a sensor in the sump? ® Yes ❑ No 0 Yes ❑ No ❑ Yes © No ❑ Yes ❑ No <br /> Does the sensor alarm when either ❑ Yes ® No ❑ NA ❑ Yea ® No ❑ NA ❑ Yes ❑ No ❑ NA Cl Ycs ❑ No ❑ NA <br /> product or water is detected? <br /> Was sensor removed for testing? 0 Yes ❑ No ❑ NA ® Ycs ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> Was Sensor properly replaced and ❑ Yes IM No 0 NA ❑ Yes ® No ❑ NA ❑ Yes ❑ Nu D NA ❑ Yes C3 No 13 NA <br /> verified functional after testing? <br /> Comments include any information on repairs madeprior to lestinje.and recommended follow-up for failed tests <br /> The sensors were reinstalled to lowest point,but not tested. <br />