Software Version Installed: N/A <br /> Cont tete the following checklist: <br /> M Yes ❑ No* I Is the audible alarm operational? <br /> 0 Yes ❑ No* Is the visual alarm operational? <br /> 0 Yes ❑ No* is the print function operational? X Not instalied- <br /> *Yes 0 No* Were all sensors visually inspected, functionally tested,and confirmed operational? <br /> Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment <br /> will not interfere with their proper operation? <br /> ❑ Yes [] No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> ❑ N/A operational? <br /> ❑Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> N/A monitoring system detects a leak,fails to operate, or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (ChecA all that apply) ❑ 5uiviplTr enc; Sensors; ❑ Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes; ❑ No. <br /> ❑Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> M N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? <br /> ❑ Yes* ® No Was any monitoring equipment replaced? If' yes, identify specific sensors, probes, or other equipment <br /> replaced and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑ Yes" Z No Was liquid found inside any secondary containment systems designed as dry systems? (Check a/1 that apply) <br /> ❑ Product; ❑ Water_ IF yes,describe causes in Section E, below. <br /> ® Yes ❑ No* Was monitoring system set-up reviewed to ensure ro er settings?Attach set up reports, if applicable <br /> •Yes ❑ Noy is all monitoring equipment oerational per manufacturer's specifications? <br /> * In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: This system consists of a single three-compartment tank monitored by an lncon 1000 panel without a <br /> printer. Inventory readings are provided by a set of in-tank "Safety Gauges" which consist of a tapemeasure with a float oa <br /> one end and a weight on the other. The piping, is a '.lack Koffelt Straight-Up' system that provides full double wall suction <br /> piping vertically from the tank to under the dispenser. The tank is directly under the island. <br />