Laserfiche WebLink
0 <br /> Q <br /> ,n <br /> N <br /> W <br /> Table 1 —Assessment of Used Oil Tank System AXOM <br /> 0 <br /> Jiffy Lube Store #2497, Stockton, CA w <br /> A <br /> Citation Requirement Assessment Findings <br /> Section 66266.190. The regulations of this article apply to owners and operators of facilities The tank does not meet the exceptions in(a)or(b), therefore <br /> Applicability. that use tank systems for transferring, storing or treating hazardous these regulations are applicable. <br /> waste,except as otherwise provided in subsections(a) and(b)of this <br /> section or in section 66265.1 of this chapter. m <br /> N <br /> (a)Tank systems that are used to transfer,store or treat hazardous <br /> waste containing no free liquids and that are situated Inside a building <br /> with an impermeable floor are exempted from the requirements of • <br /> section 66265.193 of this article. <br /> (b)Tank systems, including sumps, as defined in section 66260.10, that <br /> serve as part of a secondary containment system to collect or contain <br /> releases of hazardous wastes are exempted from the requirements in <br /> section 66265.193(a). <br /> (c)Tanks,sumps, and other collection devices used in conjunction with Not applicable, as the tank system Is not used in conjunction <br /> drip pads, as defined in section 66260,10 and regulated under Chapter with drip pads. <br /> 15, Article 17.5,shall meet the requirements of this article. <br /> Section 66265.192. (a)Owners or operators of new tank systems or components shall ensure The tank meets the requirements of this part,as demonstrated <br /> Design and that the foundation,structural support, seams, connections,and pressure below. This document is the required written assessment. <br /> Installation of New controls(if applicable)are adequately designed and that the tank system <br /> Tank Systems and has sufficient structural strength, compatibility with the waste(s)to be <br /> Components transferred, stored or treated, and corrosion protection so that it will not <br /> collapse, rupture,or fail.The owner or operator shall obtain a written No <br /> assessment reviewed and certified by an independent,qualified, •� <br /> professional engineer, registered in California in accordance with sectionPi <br /> 66270.11(d)attesting that the system has sufficient structural Integrity, Is 0) <br /> acceptable for the transferring, storing and treating of hazardous waste, w <br /> and that the tanks and containment system are suitably designed to IM <br /> achieve the requirements of this article. This assessment shall be C <br /> obtained prior to placing the tank system in service,and shall be kept on G m <br /> file at the facility.This assessment shall also include, at a minimum,the A d <br /> following information: o� <br /> o � <br /> cn <br />