Laserfiche WebLink
® NOTES: UST INSTALLATION CLIENT: <br /> O1 SLOPE CONCRETE AWAY FROM ALL MANHOLES 1" RISE OVER 12" RUN. �I <br /> /\ FIBER REINFORCEMENT TO BE USED. PREMIX UNIFORMLY THROUGHOUT <br /> CONCRETE. <br /> OREINFORCING BARS TO BE NO LESS THAN 2" AND NO MORE THAN 4" FROM <br /> SURFACE. <br /> % O REINFORCE CONCRETE SLAB AROUND MANHOLE WITH (4) #4 REBAR 60" IN <br /> LENGTH. PLACE REBAR 6" FROM SIDES OF BOX. <br /> 12 , 000 GALLON - PREMIUM UNLEADED 8 , 000 GALL0N - DIESEL SINGLE 1" CONDUIT TO EACH SUBMERSIBLE PUMP. PROVIDE SEAL-OFF AT <br /> 8" 8" 8" 8" 16 5O SUMP & BUILDING WIRING TROUGH. CONTAINS LINE VOLTAGE WIRING. LAST <br /> 16-1/2" 16-1/2" TWO FEET TO SUMPS SHALL BE PVC COATED RIGID. <br /> 16-1/2" 16-1/2" w w w <br /> 10 <br /> 10 V) n v) N ONE 1 " STANDARD MONITORING HOMERUN CONDUIT TO EACH TANK. <br /> Of REF, REF. Of x x REF. REF. FOR STANDARD MONITORING DEVICES, LOOP CONTAINMENT SUMP <br /> o 'Ad <br /> r Lw,, 42" DIA. FILL w ` _� x O SENSORS, PLLD, VAC SENSORS & TANK GAUGE TO TANK INTERSTITIAL <br /> Z N SUMP ¢ > 22" DIA, L` a > " DIA. 48" DIA TURBINE SUMP SENSOR LOCATION AND HOMERUN TO BLDG. PROVIDE SEAL-OFFS IN <br /> yj <br /> MANWAY ` - ANWAY BUILDING & PRIOR TO LEAVING HAZARDOUS AREA. ROUTE TO <br /> BRINE RESERVOIR INTRINSICALLY SAFE TROUGH IN BUILDING. CONDUITS SHALL CONTAIN <br /> AND INTERSTITIAL \ o o " 'o o p p o' I pr <br /> c " '`p p ONLY LOW VOLTAGE WIRING FOR SENSORS. LAST TWO FEET TO SUMPS <br /> C3 1 MONITOR % SHALL BE PVC COATED RIGID. ARCO o _ USE PEA GRAVEL CONSISTING OF NATURALLY ROUNDED AGGREGATE, MIN Y" <br /> aD o o r o 0 <br /> �j o ®- --®- p p -� p �o & MAX OF %" IN SIZE, FREE OF CLAY, SLAG, CINDERS, OR DEBRIS. ALL <br /> 7 BP WEST COAST PRODUCTS,LLC <br /> p �p � p fp O SUBSTITUTES MUST BE APPROVED BY MANUFACTURER'S & OWNER'S FIELD <br /> o p\ p ` p p <br /> 0 REPRESENTATIVE. <br /> ' % <br /> ANCHOR STRAP <br /> .. 1 TION (TYP.) O NOT USED. r V4 q <br /> 42" DIA. FILL <br /> 48" DIA TURBINE / SUMP 9 NOT USED. <br /> SUMP TANK WEIGHT 0 O <br /> / 99000 LBS DRY TANK PAD MINIMUM 2'-0" OFF OUTSIDE WALLS OF TANKS, AND MUST `V <br /> 10 COVER THE FOOTPRINT OF THE TANKS. REQUIRED TO PROVIDE FOR PROPER <br /> 12,600 LBS W/BRINE TANK HOLD DOWN, AND TO PREVENT ACCIDENTAL DRILLING INTO TANK. n <br /> 11 CUT CORNER WHERE MEETING ASPHALT PAVING ONLY. SQUARE CORNERS Z 2 <br /> WHERE MEETING CONCRETE. S y, <br /> -- - 1 REFER TO SITE SPECIFIC PLANS FOR ACTUAL PIPE RUNS & NUMBER OF <br /> PRODUCT LINES (1 OR 2 PER UST SUMP). G ENGEN <br /> TURBINE AND FILL SIDE SUMP CONFIGURATION SHOWN IS TYPICAL. FOR <br /> 1Q SPECIFIC DESIGN CRITERIA AT THESE SUMPS SEE ACCOMPANYING TANK 18215 72ND AVENUE SOUTH <br /> INSTALLATION SITE PLAN & SUMP DETAIL DRAWINGS NOTED ABOVE. KENT, WA 98032 <br /> OPTIONAL MANUFACTURER TANK ANCHORING OPTIONAL. CONSULT LOCAL REGULATION; VERIFY WITH (425)251-6222 <br /> SUPPLIED 18"x8"x18'<a> W R` RPR SE AT E. (425)251-8782 FAX <br /> DEADMAN (TYP. OF 4) OVERFLOW PROTECTION: UST OVERFLOW COMPLIANCE IS ACHIEVED BY USE OF CIVIL ENGINEERING, LAND PLANNING, <br /> OVERFLOW PREVENTION DROP TUBE FLAPPER VALVE SET AT 95% AND IS IN SURVEYING, ENVIRONMENTAL SERVICES <br /> ACCORDANCE WITH FEDERAL AND STATE GUIDELINES FOR UST OVERFILL <br /> 37'-9 1/4" 15 REQUIREMENTS. NO. DATE REVISION DESCRIPTION <br /> AN OVERFILL ALARM AND ACKNOWLEDGE SWITCH TIED INTO THE VEEDER ROOT 9-6-16 PERMIT SUBMITTAL <br /> UNDERGROUND TANK PLAN VIEW AUTOMATIC TANK GAUGE SYSTEM. THE MONITORING SYSTEM PROVIDES AN AUDIBLE z 12-14-16 PERMIT RESUT3AITTAL <br /> AND VISUAL ALARM WHEN THE TANK(S) ARE FILLED TO THE 90% LEVEL. <br /> SCALL: 1/2 = 1 -� 3 7-31-17 PERMIT RESUBMITTAL <br /> XX NOTE: 4 8-16-17 CONSTRUCTION RELEASE <br /> INDICATES ITEMS FOUND ON MATERIALS LIST SHEETS M.5.3.01 & M.5.3.02 <br /> C D G Q n-14-n REV. FOR coNSTRucnoN <br /> M.5.3J6 M.5.3.16 M.5.3.16 C D G H 1 7" CONCRETE SLAB AT Q <br /> M.53.12 M.53.12 M.53.12 M.53.12 2" INSIDE 3" DOUBLE M.5.3.12 M.5.3.12 M.5.3.12 M.5.3.12 87.6 LB/CF B <br /> WALL FRP VACUUM <br /> CROSSOVER TO FILL <br /> /// M.53.18 M.53.18 M.53.18 SUMP FOR VENT & 45.25' <br /> 7" THICK CONCRETE 2 3 1 1 13 VAPOR CONTINUOUS - 1 13 0 <br /> SLAB (ACT ) MONITORING. Q <br /> ASPHALT AND STONE PER H D <br /> PROJECT SPECIFICATIONS M.5.3.18 1" FRP BONDED 134 3 4 (TMP.) (2) 3.5' DIA. , <br /> ENTRY FITTING ( 1 (TMP ) 10 11 (TYP.) ( SUMPS <br /> 10 11 (TYP.) (TYP.) SEAL: <br /> a <br /> d r <br /> A�Fy <br /> e ° .. d .a. TANK DEPTH 2 4' MIR. VESSI <br /> COVE 3" PEA GRAVEL MIN. TO 1 4 1.5' GRAVEL: •1" COND. LOOP TO SUMP 18 189 2" INSIDE 3" DOUBLE - - PREVENT LOAD TRANSFER S GRUBS0 5 DIA9,000 LB 4 <br /> WALL FRP VACUUM I TO TOP OF TANK O " .,.a`' I © COLUMN <br /> J-BOX ( _ CROSSOVER TO FILL = <br /> 4" FRP RISER TO GRADE 166 a <br /> SUMP FOR VENT & w I I 5 .6T X 1.5' X 36.0' �Q <br /> VAPOR CONTINUOUS I o DEADMAN q O 1 V 1 V ".'� <br /> HOME RUN TO 6 O5 1" FRP BONDED "' rr Of \�iti <br /> 7 6 I MONITORING. I r TF -AOR <br /> BUILDING -- SO 134 m CAL, <br /> 1" FRP BONDED ' ENTRY FITTING 12" x <br /> DUAL FLOAT HYDROSTATIC 34 <br /> 0 ENTRY FITTING (TIP•) 13'-6" <br /> MONITORING SENSOR O (TYP.) 6 Z 5 = <br /> HYDROSTATIC <br /> TO TURBINE <br /> RESERVOIR =-� - ----- _ SUMP <br /> ( __ ____�._ - -_ ..._ . . . Q � BUOYANCY CALCULATIONS Z <br /> SLOPE SIDES OF TANK HOLE OR Q - I CALCULATION BASED ON SUBMERGED WEIGHT OF ALL MATERIALS: rn <br /> USE SHORING FOR ALL TANK - <br /> EXCAVATIONS IN ACCORDANCE WITH , �� __�= _ _ -` TANK WITH SPHERICAL ENDS, 10.5' O.A. DIAM. (10' NOMINAL) o <br /> OSHA 1926 SUBPART P, OSHA / '� \ TANK LENGTH: 37' 9-1/4" TANK DIAMETER 10'-6" <br /> STANDARDS - EXCAVATIONS; FINAL \ _ / \ / �' TRY 36'-0" DEADMAN, EACH SIDE, 18" WIDE X 8" HIGH o <br /> RULE OCTOBER 1, 1989 <br /> EMPTY TANK UPLIFT = 19,666 GAL = 2629 CU FT <br /> \ DEVELOPMENT INFORMATION: � <br /> co 7.48 GAL./CF <br /> / 19 EXTRACTOR FITTING 20 EXTRACTOR FITTING 2629 CU FT X 62.4 LBS/CF = 164,049 LBS (DISPLACED WATER) ARCO NTI <br /> IL <br /> Q5 I ( �� II TANK SUMP UPLIFT = (2) X 3.14 X 2.0'2X 4' = 100.5 CU FT MODIFIED <br /> OVERFILL PROTECTION OVERFILL PROTE 10 / + (2) X 3.14 X 1.75'2X 4' = 77.0 CU FT N <br /> 3000 am/pm <br /> DROP TUBE SET AT 41 15 I DRO T E S A 41 5 I I ( \\ ? 177.5 CU FT p <br /> \\ I 95% (ACT.) 5% ( P. I I „` Q 177.5 CF X 62.4 LBS/CU FT = 11,076 LBS (DISPLACED WATER) w/ 26x65 CAR WASH o <br /> \ TOTAL TANK UPLIFT = 164,049 LBS + 11;076 LBS = 175.125 LBS } FUEL CANOPY w/ 8 MPD's <br /> ( I 04 TANK LEVEL GAUGE W/ 04 TANK LEVEL GAUGE W \ <br /> 7 BACKFILL WITH PEAGRAVEL I 2" FLOAT KIT. OVERFILL I I 2" FLOAT KIT. OVERFILL O SITE ADDRESS: ` <br /> \\ \\ PER TANK MANUFACTURER <br /> SPECIFICATIONS. FACT.) ( I P ITY I ALARM AT 90% CAPACITY I //\//\ I E <br /> // 05 ALARM AT 90% O6 II \\/\\/ 1a HOLD DOWN CALCULATION <br /> �� C) � TANK SLAB: .58' X 13.5' X 45.25' = 354.3 CU FT TRINITY PARKWAY <br /> O 354.3 CU FT X 87.6 LBS/CU FT = 31.037 LBS @ SCOTT CREEK DRIVE o <br /> 12"x24"x11GA STEEL STRIKER \\ \\� 2 CUBED BACKFILL ABOVE TANK: STOCKTON,CA <br /> PLATES TYP. UNDER ALL OPENINGS / / \//\//\� 4' X 10.5' X 37.75' 1,585.5 CU FT - 177.5 CU FT = 1,408 CF ---- CP <br /> W/ MANWAYS ON FIBERGLASS TANK I I / / / 1,408 CU FT X 57.6 LBS/ CU FT = $,yQQ LESS + FACILITY # TBD <br /> (BY TANK MANF.) / \\ \\//� (� CURVED BACKFILL ABOVE TANK: <br /> z \ \\/ \\ a N 3.14 X 5.25'ZX 37.75' = 3,267.0 CU FT DESIGNED BY: ALLIANCE Z&DM: Lo <br /> o `//\// �� 12"x12"xt 1GA STEEL STRIKER PLATES x X /// j\ 10.5' X 10.5' X 37.75' = 4,161.9 CU FT O ECIa BY., BP REPM: <br /> TYP. UNDER ALL OPENINGS W/O Q . / //\\//\\i 4,161.9 CU FT - 3,267.0 CU Fi = 894.2 CU FT= 447.45 CU FT DRAWN BV: NUANCE PIA: <br /> Z MANWAYS ON FIBERGLASS TANK N z `' N z `_ ' //%//% <br /> o m w w ro, ' °. " (BY TANK MANE} Lq <br /> "o- \ \ 447.45 CU FTX 57.6 LBS CU FT = 25.773 LBS <br /> \\ / VE PR QCT NO• <br /> 1.5'AVXL 1�OLUXN36 OOVX DEADM FT CU FT <br /> „ ": b:. .. ;, o- 1,566 CU FTX 57.6 LBS/ CU FT = 90.202 LBS DRAW NG TITLE: <br /> .�, J .. 16700 / <br /> o N EA GRAVEL ::.�..•ro. ;• ., <br /> .:. 1 .. ro.• .. ro.. ro.. ,.P.. ,a °_ a.,. _ N <br /> ro TRAPPER SCREEN . ro': :. . a' =a TRAPP <br /> \ e..•.. .. .o- ...o•• :•tl' , a ER SCREEN \ \ <br /> .. n „:.�:•.'r. •._.�..."r. CRETE DEADMEN• <br /> t os ro w:P:•` G TYPICAL 12,000/8,000 GALLAN <br /> .. 7 INSTALLED OVER .. .. . . <br /> .$ ON <br /> tl'- <br /> TCP. w <br /> ro :. <br /> p a P / / <br /> O pea <br /> ...�. .. .. .. .. .6T X 1.5' X 36.0' 36.2 CU FT <br /> lY . <br /> COMPACTED SOIL 9 P ... ro -. . •, ro• ,° • :,:. •:: b:. : •:. \ \ DOUBLE WALL FIBER <br /> .. °.. • .. w b w ° ... . < .. w . . . . .. I OU GLASS TANK <br /> / 36.2 FT X 87.6 LBS/ CU FT X (2) = 6.342 BSDETAILS - <br /> \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ INSTALLATION o <br /> 6 DRY WEIGHT OF TANK: 9.000 LBS <br /> i TOTAL HOLD DOWN: 243.454 LBS SHEET NO: <br /> vo <br /> END OF TANK <br /> 2' MIN. op TANK SIZE VARIES WITH MANUFACTURER AND MODEL NUMBER 2' MI TOTAL HOLD DOWN: 243.454 LBS = 1.39 SAFETY FACTOR <br /> 10 10 TOTAL TANK UPLIFT: 175,125 LBS RUN <br /> A: UNDERGROUND TANK SECTION DETAIL BUOYANCY CA C. 20000 GAL. TANK <br /> SCALE: 1/2" = 1 '-O" a <br /> SCA E: NTS a <br /> LL <br />