Laserfiche WebLink
{ SAN JOAQUIN LOCAL DISTRICT <br /> 1601 East Haul venue <br /> Phone 466- 1 <br /> STOCKTON, CALIFORNIA Page 1 Of 2 <br /> INSPECTION REPORT <br /> Owner/operator California Fuels Date-31S=8519— <br /> Locatio 221 <br /> Facility Name Connell Motor Truck Co. — <br /> , i X>X a. Underground storage tank <br /> 11aion ,Dans for four 10,000 gal . motor vehicle fuel <br /> instatanks are approved with the condition that the following <br /> information be provided and/or requirements met prior to <br /> o eration: <br /> (To be provided by contractor) <br /> 1 provide drawing and specifications on EBW 704-700 <br /> overfi <br /> 2. Indicate model # for TC-3000 monitoring device. <br /> 7j Fiberglass laminated double wall steel tanks to be <br /> holiday tested prior Ln pl r•inn in axravat,nn_saLl <br /> to schedule inspection 24 hours prior to test. <br /> ,Q Primary and secondary containers to ho +acted prior <br /> to covering, call to schedule inspection 24 hrs prior <br /> to test. <br /> 5. Note: Precision test required-Q tpm <br /> prior to placing in operation, including piping. <br /> 6 Note Existing single wall piping (suction) must <br /> have cathodic protection a de_ ____.+;trio ..;th <br /> tank system. <br /> --------------- <br /> (To baprovidel hY Own <br /> 1 . Owner or operator must submit completed underground <br /> storage tank operating permit applications <br /> Received Notim: <br /> J;Z; <br /> .D., MPH, Di s[r [ ltk EEi er <br /> gistered Sanitarian 7/85 <br /> EH 00 20 <br />