Laserfiche WebLink
0 0 RECEIVEL <br /> SWRCB,January 2002 MAR $aQe2015 of_ <br /> 4. TANK ANNULAR TESTING ENVIRONMENTAL_ <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard ❑Pro0fidliall Engineer <br /> ❑Other(Specify) <br /> Test Method Used: Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Gast Vacuum PumpNacuum Gauge in Hg. Equipment Resolution: -'/3"x-301-1g. <br /> Tank#1&2 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' No <br /> Tank Capacity: 15K Split 12/3 <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: XERXES <br /> Product Stored: Regular 87/Super 91 <br /> Wait time between applying 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 9:35 <br /> Initial Reading(R[): -10 Hg. <br /> Test End Time: 10:35 <br /> Final Reading(RF): -10 Hg. <br /> Test Duration: I Hour <br /> Change in Reading(RF-Ri): 0 Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2 Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? No <br /> Was sensor properly replaced and N!A <br /> verified functional after testin ? <br /> Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> 15K Split Compartment Tank, 12K Regular 87/3K Super 91. Single Annular! <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />