SWRCB,January 2002 • Page_of_ <br /> 7. UNDER-DISPENSER CONTAINMENT C TESTING 10 - <br /> Test Method Developed By: D UDC Manufacturer ®Industry Standard D Professional Engineer <br /> D Other(Spec) <br /> Test Method Used: D Pressure . D Vacuum ®Hydrostatic <br /> D Other(Spew) <br /> Test Equipment Used:INCON Equipment Resolution:.0001 <br /> UDC#'h UDC#% UDC#5/6 UDC#7/8 <br /> UDC Manufacturer. Unk Unk Unk Unk <br /> UDC Material: Fiber Fiber Fiber Fiber <br /> UDC Depth: 24" 24" 24" 24" <br /> Height from UDC Bottom to Top 10" 10" 10" 10" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 12" 12" 12" 12" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Clean/Dry Clean/Dry Clean/Dry Clean/Dry <br /> testing: <br /> Portion of UDC Tested 18" 18" 18" 18" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both D Yes D No DNA DYes 01-b DNA D Yes D No DNA D Yes D No DNA <br /> product and water)?* <br /> Turbine shutdown response time <br /> Is system programmed for fail- D Yes p No DNA DYes D No DNA D Yes D No DNA D Yes D No DNA <br /> safe shutdown?* <br /> Was fail-safe verified to be D Yes D No D NA DYes D No DNA D Yes D No DNA D Yes D No DNA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 1119 1119 <br /> Initial Reading(RO: 6.1170 4.9444 <br /> Test End Time: 1134 1134 <br /> Final Reading(RF): 6.1156 4.9441 <br /> Test Duration: 15 min 15 min 15 min 15 rain <br /> Change in Reading(RF-Rt): .0014 .0003 <br /> Pass/Fail Threshold or Criteria 002 .002 .002 .002 <br /> Test Result: Pass q;Fail D Pass p Fall. 0:Pass l7 Fail 0 Pass D Fail <br /> Was sensor removed for testing? DYes D No DNA D Yes D No DNA DYes 01-b DNA D Yes D No D NA <br /> Was sensor properly replaced and DYes D No DNA DYes D No DNA Dyes ONO DNA DYes D No DNA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-upforfaded tests) <br /> Dispenser % and 7/8 not tested due to torn secondary boots on udc sump. <br /> QQIRaii/n <br /> CIYCU <br /> 811 IRON 11 maimll& <br /> If the entire depth of the UDC is not tested, specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />