Laserfiche WebLink
'F INTEG'NITY TANK TESTING SER�ACES <br /> P. O. BOX 691736, STOCKTON, CA. 95269 <br /> August 27, 1993 <br /> Port of Stockton Site: 2201 W. Washington <br /> P. O. Box 2089 <br /> Stockton, Ca. 95201 <br /> Dear Mr. Aldo Freggiaro, <br /> Following is a summary of the precision testing we recently conducted on your <br /> underground storage at the above site: <br /> Enclosed are copies of the test worksheet, graphs, and/or computer generated <br /> summations for your submittal to the appropriate governmental agency. <br /> A tank system may be considered tight, according to the current regulations if the test <br /> results shown below do not exceed 0.05 GPH. If the results are beyond this parameter <br /> an unauthorized release may have occurred, and you should consider taking remedial <br /> action. <br /> Tank#/Location Product Contained Loss/Gain GPH Tank Tight <br /> West Tank Diesel Fuel -.037 Yes <br /> East Tank Gasoline +.002 Yes <br /> Please advise if you needed additional assistance or information <br /> Sincerely, <br /> 134 &44r e <br /> W. N. Savage <br /> Certified Tester <br /> 1 <br /> �j1G ;r 193 <br /> FORT OF S T ON O-M <br /> STOCKTON (209) 474-1375 TOLL FREE (800) 262-8378 <br />