Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: _Sump Manufacturer Industry Standard X Professional Engineer <br /> E Other(Specify) _ <br /> Test Method Used: Pressure Vacuum X Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> Sump# 1-87 Sump#2-91 Sump# Sump# <br /> Sump Diameter: 42" 42" <br /> Sump Depth: 45" 45" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 21" 25" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 21" 15" <br /> Electrical Penetration: r r= L) <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' Water Line 23" Water Line 27" 2017 <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes <br /> ENTAL HEAI-T <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe Yes Yes <br /> shutdown?` <br /> Was fail-safe verified to be No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 9:37 9:42 <br /> Initial Reading(Ri): .001 .001 <br /> Test End Time: 10:07 10:12 <br /> Final Reading(RF): .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading(RF-Ri): 0 0 <br /> Pass/Fail Threshold or Criteria: .005130 Minutes .005130 Minutes <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and yes Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' if the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LO-160) <br />