INDIVIDLRL TANK INFORMATION AN EST RESULTS <br /> JLPP Tanknology <br /> 8900 SHOAL CREEK, BUILDING 200 <br /> TEST DATE: 11/06/03 AUSTIN,TEXAS 78757(512)451-6334 WORK ORDER NUMBER: 2228896 <br /> CLIENT: USA PETROLEUM SITE: USA #65 <br /> Tank ID: 12K 2 Tank manifolded: NO Bottom to top fill in inches: <br /> Product: PLUS Vent manifolded: No Bottom to grade in inches: <br /> Capacity in gallons: 12,032 Vapor recovery manifolded: yES Fill pipe length in inches: <br /> Diameter in inches: 96.00 Overfill protection: yEs Fill pipe diameter in inches: 4.0 <br /> Length in inches: 389 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: ATG Stage 11 vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> MEEMOMM <br /> WEE <br /> PSI at�tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> UFT/OFT: Make: RED JACKET <br /> Fluid volume in gallons: Model: Fx1v <br /> Tank water level in inches: S/N: 406020215 <br /> Test time: NOT Open time in sec: 4.00 <br /> Number of thermisters: Holding <br /> Specific gravity: TESTED psi: 20 NOT <br /> Resiliency cc: 110 TESTED <br /> Water table depth in inches: est leak rate ml/m: 189.0 <br /> Determined by(method): Metering psi: 12 <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> t <br /> +! tl <br /> Test time: Material: ENVIRON <br /> Ullage volume: Diameter(in): 1.5 <br /> Ullage pressure: Length (ft): 120.0 <br /> Results: Test psi: 50 <br /> Bleedback cc: 160 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Test 1:Start time: 08:40 <br /> Time of test 1: Finish psi: 50 NOT NOT NOT <br /> Temperature: NOT Vol change cc: 0 <br /> Test 2:Start time: 08:50 TESTED TESTED TESTED <br /> Flow rate(cfh): TESTED Finish psi: 50 <br /> Time of test 2: Vol change cc: 0 <br /> Temperature: Test 3:Start time: 09:00 <br /> Finish psi: 50 <br /> Flow rate(cfh): Vol change cc: 0 <br /> Time of test 3: Final gph: 0.000 <br /> Temperature: Result: PASS <br /> Flow rate(cfh): Pump type: PRESSURE <br /> COMMENTS Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: yEs <br /> Printed 11/13/200314:44 SBOWERS <br />