• Page_of <br /> 7.UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: X UDC Manufacturer ❑Industry Standard U 7ostoa <br /> ineer <br /> ❑Other(Spec) <br /> Test Method Uses: ❑Pressure ❑Vacuum X <br /> 00 ther(Specify) <br /> Measuring P:quipment Used for Tcstuu: UST ZOOOP _ .._ <br /> UDC#7/8 <br /> UDC Manufacturer: BRAVO <br /> UDC Material: STEEL <br /> UDC Depth: 12" <br /> Height from UDC Bottom to Bottom of Box <br /> Highest Piping Penetration: <br /> Height from UDC Bottom to Bottom of Box <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to DIRTY/FAIR <br /> testing: <br /> Portion of UDC Tested ENTIRE BOX <br /> Wait time between applying @10 MIN <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 1015 <br /> Initial Readin (Rt): •5782 <br /> Test End Time: 1021 <br /> Final Reading(RF): .5777 <br /> Test Duration: 6MIN <br /> Chane in Reading(RF-Rt): -.0005 <br /> Pass/Fail Threshold: +/-.001 <br /> Test Result: PASS <br /> Was sensor removed for YES <br /> testin ? <br /> Was sensor properly replaced YES <br /> after testin ? <br /> Comments (include information on repairs made prior to testing) <br /> SWRCB December 2001 <br />