Laserfiche WebLink
• • Page_of <br /> 7. UNDER-DISPENSER CONTAINMENT DC TESTING <br /> Test Method Developed By: X UDC Manufacturer O Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Uses: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Specify) <br /> Measurin, Fquiprnent Used for Testing UST <br /> — — F — UDC#1/2 — UDC#3/4 UDC#5/6 <br /> UDC Manufacturer: BRAVO <br /> BRAVO BRAVO <br /> STEEL STEEL STEEL <br /> UDC Material: 12" <br /> UDC Depth: 12" 12" <br /> Height from UDC Bottom to Bottom of Box I Bottom of Box Bottom of Box <br /> Highest Piping Penetration: <br /> Height from UDC Bottom to Bottom of Box Bottom of Box Bottom of Box <br /> Lowest Electrical Penetration: DIRTY FAIR <br /> Condition of UDC prior to DIRTY/FAIR DIRTY/FAIR <br /> testing: <br /> Portion of UDC Tested ENTIRE BOX ENTIRE BOX ENTIRE BOX <br /> Wait time between applying @10 MIN @10 MIN @10 MIN <br /> pressure/vacuum/water and starting <br /> test 0952 <br /> Test Start Time: 0916 0935 <br /> Initial Reading(R,): .0888 ;=6MIN6MIN <br /> .8710 <br /> Test End Time: 0922 0958 <br /> 0887 .8707 <br /> Final Reading(RF): <br /> Test Duration: 6M�Chane in Readin RF-R,): -.0001 -.0003 <br /> Pass/Fail Threshold: +/-.001 +/-.001 <br /> Test Result: PASS PASS PASS <br /> Was sensor removed for YES YES YES <br /> testing? YES <br /> Was sensor properly replaced YES YES <br /> after testin ? <br /> Comments (include information on repairs made prior to testing) <br /> Floats removed for testin and then replaced. <br /> December 2001 <br /> SWRCB <br />