Laserfiche WebLink
Executive Order VR-101-D, Phil-Tite Phase I Vapor Recovery System, Exhibit 2, Page 3 <br /> capacity. The drop tube overfill device is not a required component of the vapor recovery <br /> system, but may be installed as an optional component of the system. Other requirements <br /> may apply. <br /> 2. The leak rate of the overfill device shall not exceed 0.17 CFH at 2.00 inches 1-120when <br /> tested as in accordance with the latest adopted version of TP-201.1 D, Leak Rate of Drop <br /> Tube Overfill Prevention Device and Spill Container Drain Valves. <br /> Threaded Riser Adaptor <br /> The Threaded Riser Adaptor shall provide a machined surface on which a gasket can seal and <br /> ensures that the seal is not compromised by an improperly cut or improperly finished riser. A <br /> Threaded Riser adaptor shall be installed on the following required connections. As an option, <br /> the adaptor may be installed on other connections. <br /> a. Product Spill Container(required) <br /> b. Vapor Recovery Spill Container(required) <br /> c. Tank Gauging Components (required) <br /> Ball Float Vent Valve <br /> A ball float vent valve (ball float) is designed to restrict the flow of a gasoline delivery by using <br /> back pressure when the storage tank levels exceed a specified level. If installed, a ball float <br /> must be installed at each vapor and vent connection to the tank. Ball floats are not required <br /> components of the vapor recovery system, but may be installed as optional components for <br /> vapor recovery; other requirements may apply. <br /> Vapor Recovery Riser Offset <br /> 1. The vapor recovery tank riser may be offset from the tank connection to the vapor <br /> recovery Spill Container provided that the maximum horizontal distance (offset distance) <br /> does not exceed twenty (20) inches. One example of an offset is shown in Figure 2E. <br /> 2. A vapor recovery riser shall be offset up to 20 inches horizontal distance with use of <br /> commercially available,four(4) inch steel pipe fittings, a Phil-Tite Model M 6050 Vapor <br /> Riser Offset, or a combination of the two products. An example of a Phil-Tite Model <br /> M-6050 configuration is shown in Figure 2E. <br /> Tank Gauge Port Components <br /> The tank gauge adaptor and cap are paired. Therefore, an adaptor manufactured by one <br /> company shall be used only with a cap manufactured by the same company. <br /> Connections and Fittings <br /> All connections and fittings not specifically certified with an allowable leak rate shall not leak. <br /> The absence of vapor leaks may be verified with the use of commercial liquid leak detection <br /> solution (LDS), or by bagging,when the vapor containment space of the underground storage <br /> tank is subjected to a non-zero gauge pressure. (Note: leak detection solution will detect leaks <br /> only when positive gauge pressure exists). <br />