Executive Order G-70.164,Exhibit 2,page 2 <br /> 4. Nozzles shall be 100 percent performance checked,at the factory, including checks of all <br /> shutoff mechanisms and of the integrity of the vapor path. The maximum allowable leak <br /> rate for nozzles with internal vapor valves during this factory performance test shall not <br /> exceed the following: <br /> 0.038 CFH at a pressure of at least two (2) inches water column <br /> 0.005 CFH at a vacuum pf at,least forty (40) inches tnrater column. <br /> 5. Leaded and unleaded spouts are interchangeable. <br /> Flow Act{tpjQd vapor Valves <br /> 1. A flow,astuated vapor valve,.as listed in Exhibit 1, sha11 be installed in conjuction with each <br /> nozzle :Which does not have an .integral vapor valve. Vapor valves shall be 100 percent <br /> perforrraance checked pt:the -fAOpry. The .maximum allowable weak rate for vapor valves <br /> during his factoryperformance test shallnotpxceed,the following: <br /> 0.038 CFH,at a plesswre;af at least dwo (2) inches,water column <br /> 0.005 CFt-1 at a vacuum of at_least forty(4p)jnc4ps Wpter column. <br /> BreakawavQ. otinas <br /> 1. Breakwy couplings arp opt(onal. if they pre irastaped, or4y certified breakaways with a <br /> valve,y&'ch doses the .vapor path Mien peparated shall be used for nozzles with internal <br /> vapor vi#yps. Mate: a brea{catyay yrith a xapor Valve$hat etoses uponsepar�?tion is not <br /> requlrect ff tl a CFP-1 how cgr>trpl vatye (or any other remote vappr :valve CARjB certified <br /> with the yCP-3A.system) is used because the vappr Rath-remains clpsed unless there is <br /> gasolirke kQW. <br /> Inverted AQpiaJ Hoses <br /> 1. The maximum length of the-hpse shall be 14 feet. <br /> 2. The,length of hose which may 4e in contact with the jsland and/or grown,d when the nozzle <br /> is property mounted on the dispenser is limed to six (6)inches. <br /> Collection Unit(Vapory Pump) <br /> 1. The VGP3A system shall operate With a certified collectjon.unit (pump) specified in Exhibit <br /> 1 capable of meeting the .air to liquid (A/L) ratio specified .below. The A/L ratio of the <br /> system, measured at a flowrate of at least six gallons per rrlinute (6 gpm), shall be within <br /> the values listed in the following .table (linear interpolation may be used to calculate <br /> intermediate values). Any fueling point not capable of demonstrating compliance with this <br /> performance standard shall be deemed defective and removed from service. The A/L ratio <br /> shall be determined by a GARB-approved or district-approved test procedure. (Draft <br /> procedure TP-201.5 may be used until an A/L ratio test procedure is adopted by CARB). <br /> Alternative test procedures may be used if they are determined by the Executive Officer to <br /> yield comparable results. <br />