Laserfiche WebLink
6.3 Measure the gallons of gasoline present in each underground storage tank <br /> and determine the actual capacity of each storage tank from facility <br /> records. Calculate the ullage space for each tank by subtracting the <br /> gasoline gallonage present from the actual tank capacity. The minimum <br /> ullage during the test shall be 25 percent of the tank capacity or 500 <br /> gallons, whichever is greater. The total ullage shall not exceed 25,000 <br /> gallons. <br /> 6.4 For two-point Phase I systems, this test shall be conducted with the dust <br /> cap removed from the vapor coupler. This is necessary to determine the <br /> vapor tightness of the Phase I vapor poppet. See Section 6.7 if this test is <br /> to be conducted at the Phase I vapor coupler. <br /> 6.4.1 For coaxial Phase I systems this test shall be conducted with the <br /> dust cap removed from the Phase I coupler. This is necessary to <br /> insure the vapor tightness of the Phase I vapor poppet. <br /> 6.4.2 Verify that the liquid level in the storage tank is at least four (4) <br /> inches above the highest opening at the bottom of the submerged <br /> drop tube. <br /> 6.5 If the Phase I containment box is equipped with a drain valve, the valve <br /> assembly may be cleaned and lubricated prior to the test. This test shall, <br /> however, be conducted with the drain valve installed and the manhole <br /> cover removed. See subsection 7.4.1 for further details regarding <br /> containment box drain valves. <br /> 6.6 If the test is to be conducted at a Phase II vapor riser, disconnect the <br /> dispenser end of one vapor recovery hose and install the 'T' connector <br /> assembly (see Figure 3-1). Connect the nitrogen gas supply (do not use <br /> air) and the pressure measuring device to the 'T' connector. <br /> 6.6.1 For those Phase II systems utilizing a dispenser mounted remote <br /> vapor check valve, the 'T' connector assembly shall be installed <br /> on the vapor riser side of the check valve. <br /> 6.7 If this test is to be conducted at the Phase I vapor coupler on a two-point <br /> Phase I system, the procedures set forth in subsections 6.7.1 and 6.7.2 <br /> shall be successfully completed prior to testing. The static pressure <br /> integrity test shall not be conducted at the Phase I coupler at facilities <br /> equipped with coaxial Phase I systems. <br /> 6.7.1 Connect the Vapor Coupler Integrity Assembly to the Phase I <br /> vapor coupler. Connect the Vapor Coupler Test Assembly. <br /> Connect the nitrogen supply to the assembly and carefully <br /> pressurize the internal volume of the assembly to two (2.0) inches <br /> H2O. Start the stopwatch. Record the final pressure after one <br /> minute. <br /> G-70-164 Exhibit 3-5 <br />