Laserfiche WebLink
SWRCB,January 2002 Page <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes: <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested: <br /> Test Method Developed By: F-1 Spill Bucket Manufacturer Industry Standard Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: F] Pressure Vacuum Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Spill Box# 1 Spill Box# 1 Spill Box# 2 Spill Box# 2 <br /> Bucket Diameter: 14 14 14 14 <br /> Bucket Depth: 8 6 6 a <br /> Wait time between applying <br /> pressure/vacuum/water and 30 30 30 30 <br /> starting test: <br /> Test Start Time: 0940 0940 0940 0940 <br /> Initial Reading(RI ): 5 6 6 4 <br /> Test End Time: 1040 1040 1040 1040 <br /> Final Reading(RF ): 5 6 6 4 <br /> Test Duration: 1 hr 1 hr 1 hr 1 hr <br /> Chane in Reading(R F Rt ) 0 0 0 0 <br /> Pass/Fail Threshold or 0 0 0 0 <br /> Criteria: <br /> Test Result: 1E Pass D Fail Pass D Fail Pass U Fail x Pass Li Fail <br /> Comments - (include information on repairs made prior to testing, and recontmencled fi)llow-up for,fitiled tests) <br />