t <br /> D. Results of 7esting/Semicing JAN 14 20:5 <br /> Software Version Installed VR 1.01 EN11YL]OhlMENTf, - <br /> Com ete the followingchecklist: Irl' MVI_.. <br /> X Yes ❑ No- Is the audible alarm operational? <br /> X Yes ❑ No' Is the visual alarm operational? <br /> X Yes No' Were all sensors visually impacted,functionally tested,and confirmed operational? <br /> X Yes = No' Were all sensors installed at lowest point of secondary containment and poskioned so that other equipment will not interfere with their <br /> rimmer o ration? <br /> Yes ❑ NO' If alarms are relayed to a remote monitoring station,Is all communications equipment(e.g.modem)operational? <br /> X WA <br /> X Yes ❑ No' For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system <br /> ❑ WA detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate positive shut down? (Check all that apply) <br /> X Sump/Trench Sensors; X Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor <br /> failureldisconnection? X Yes; No. <br /> X Yes ❑ No' For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e. no mechanical overfill prevention <br /> WA valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and operating properly? If so,at what percent <br /> of tank capacity does the alarm trigger? 95 % <br /> X Yes• No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the <br /> manufacturer name and model for all replacement parts in Section E,below. <br /> X Yes' No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)❑Product; �❑Water. If <br /> as,describe causes in Section E,below. <br /> X Yes _ No' Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,i1 applicable <br /> X Yes No' Is all monitoring equipment operational per manufacturer's specifications? <br /> In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: 1 CUP H2O FOUND IN DIESEL STP SUMP, 1.6 GAL DIESEL FOUND IN DISP 11-12 UDC BOTTOM OF 9-10 UDC <br /> WAS WET WITH DIESEL.DIESEL DISP#12 WAS PLACED OUT OF SERVICES FOR REPAIRS. <br /> L2 DISP 1-2 ANNULAR[MIDDLE VR 304 X PASS sensor was in fuel alarm upon arrival sensor was replaced and retested <br /> L4 DISP 3.4 ANNULAR[MODLE VR 304 X PASS <br /> L 6 DISP 5-6 ANNULAR[MIDDLE VR 304 X PASS <br /> L 8 DISP 7-8 ANNULAR[MIDDLE VR 304 X PASS <br /> L 10 DISP 9-10 ANNULAR[MIDDLE VR 304 X PASS <br /> L 12 DISP 11-12 ANNULAR[MODLE VR 304 X PASS <br /> L 13 VENT DOX[MODLE VR 208 X PASS <br /> L 14 VENT BOX ANNULAR[MODLE VR 304 X PASS <br /> L 16 87 STP SUMP ANNULAR[MODEL VR 304 X PASS <br /> L 18 87 FILL SUMP ANNULAR[MODLE VR 304 X PASS <br /> L 20 91 STP SUMP ANNULAR[MIDDLE VR 304 X PASS <br /> L 22 91 FILL SUMP ANNULAR[MODLE VR 304 X PASS <br /> L 24 DIESEL STP SUMP ANNULAR[MODLE VR 304 X PASS <br /> L 26 DIESEL FILL SUMP ANNULAR[MODLE VR 304 X PASS <br /> Monitoring System Certification Page 2 of 4 12107 <br /> 2 2/21/07 <br />