Laserfiche WebLink
Veeder-Root Line Leak Application Guide <br /> MAXXUM PUMPS <br /> 1. Thread the DPLLD or PLLD transducer into the 2-inch opening of the transducer port. <br /> ® IMPORTANT! Seal any pipe threads using a UL-classified, non-toxic pipe sealant suitable for the fuel involved. <br /> 2. If any in-line check valves or a Big-Flo Diaphragm Valve are installed in the line,they must be removed. <br /> 3. Verify that the TLS 350 Series Console has Version x19 or later software(TLS-450 Series Consoles Version 1 or later <br /> software). <br /> Junction box Seal-off, epoxy seal per NFPA spec <br /> (customer supplied) (customer supplied) <br /> DPLLD or PLLD <br /> transducer 1 n 2" <br /> Transducer <br /> port <br /> 0 ® conduit to console <br /> (customer supplied) <br /> o � <br /> i <br /> — vnaune.xum.ays <br /> FE PETRO HIGH CAPACITY PUMPS <br /> 1. Install a reducing tee(customer supplied)in either of the 3-inch discharge ports of the pump with the 2-inch port facing up. <br /> 2. Thread the D/PLLD transducer into the 2-inch port on the tee fitting. <br /> IMPORTANT! Seal any pipe threads using a UL-classified, non-toxic pipe sealant suitable for the fuel involved. <br /> 3. Install a model"R"relief valve into the pump if one is not already present. <br /> 13 <br />