Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: Sump Manufacturer Industry Standard X Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure Vacuum X Hydrostatic <br /> Other(Spec) _ <br /> Test Equipment Used:INCON TS-STS Equipment Resolution: <br /> „. <br /> Sump# 191 Tl Sump# 2 91 T2 Sump# 3 87 Sump#4 DIESEL <br /> Sump Diameter: 42" 42" 42" 42" <br /> Sump Depth: 38" 36" 36" 36" <br /> Sump Material: FRP FRP FRP FRP <br /> FRPHeight from Tank Top to Top 18" 12" 17" 17" <br /> of Highest Piping Penetration: <br /> Height from Tank Top to Lowest 10" 9" 13" 9" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: CLEAN/DRY CLEAN/DRY CLEAN/DRY CLEAN/DRY <br /> Portion of Sump Tested' 22" 16" 20" 20" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X Yes D No D NA X Yes D No D NA X Yes D No DNA XYes D No DNA <br /> product and water)? <br /> ater)?" <br /> Turbine shutdown response time 15 see 15 see 15 see 15 see <br /> Is system programmed for fail-safe X Yes D No D NA X Yes D No D NA X Yes ❑No DNA XYes DNo DNA <br /> shutdown?" <br /> Was fail-safe verified to be XYes DNo DNA XYes DNo DNA XYes ❑No DNA XYes DNo DNA <br /> o erational7" <br /> Wait time between applying <br /> pressure/vacuum/water and starting 30 min 30 min 30 min 30 min <br /> test: <br /> Test Start Time: 10:38 AM 10:58 AM 10:38 AM 10:38 AM <br /> Initial Reading(Rj): 5.8045 5.2461 4.4043 5.7318 <br /> Test End Time: 10:53 AM 11:13 AM 10:53 AM 10:53 AM <br /> Final Reading(RF): 5.8036 5.2468 4.4031 5.7307 <br /> Test Duration: 15 min 15 min 15 min 15 min <br /> Change in Reading(RF R): .0009 .0007 .0012 .0011 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002 002 <br /> Test Result: X Pass D Fail X Pass D Fail X Pass D Fail X Pass ❑Fail <br /> Was sensor removed for testing? XYes D No DNA XYes D No DNA XYes D No DNA XYes ❑No ❑NA <br /> Was sensor properly replaced and XYes DNo DNA XYes []No DNA XYes DNo ON XYes ❑No ❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommendedfollow-up forfailed tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />