Laserfiche WebLink
D. Results of Testing/Servicing WP 19 <br /> X1017 <br /> Software Version Installed: 329.01 ENVIRONMENTALHEALTH <br /> Complete the following checklist: <br /> PERMITISERVICES <br /> ® Yes ❑ No' Is the audible alarm operational? <br /> ® Yes ❑ No' Is the visual alarm operational? <br /> ® Yes ❑ No' Were all sensors visually inspected,functionally tested,and Confirmed operational? <br /> EI Yes ❑ No' Were all sensors installed at lowest point of secondary Containment and positioned so that other equipment will not interfere with their proper <br /> operation? <br /> ❑ Yes ❑ No' If alarms are relayed to a remote monitoring station,is all Communications equipment(e.g.,modem)operational? <br /> R NIA <br /> ® Yes ❑ No' For pressurized piping systems,does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, <br /> ❑ N/A fails to operate, or is electrically disconnected? If yes:which sensors initiate positive shut-down? (Check all that apply) ® Sump/Trench <br /> Sensors; ®Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks @nd sensor failure/disconnecrhon? ®Yes; ❑No. <br /> ® Yes ❑ No' For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e., no mechanical overfill prevention valve is <br /> ❑ NIA installed),Is the oveMll warning alarm visible and audible at the tank fill point(s)and operating property? If so,at what percent of tank capacity <br /> does the alarm trigger? 90% <br /> ❑ Yes ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced and list the manufacturer name <br /> and model for all replacement parts in Section E,below. <br /> ®Yes' ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ®Water. If yes,describe Causes in Section E,below. <br /> ® Yes ❑ No' Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ® Yes ❑ No' Is all monitoring equipment operational per manufacturer's specifications? <br /> In Section E below,describe how and when these de0ciencies were or will be corrected. <br /> E. Comments: WATER FOUND IN ALL BUT 89 STP SUMP. DISP 5-6 ALSO HAD WATER <br /> WATER REMOVED BY ELITE IV <br /> All Repairs and retest from this day will be done by Elite IV <br /> Monitoring System Certification Page 2 of 4 2/21/07 <br />