Revised Scope of Work SR#0071876 Arch Rd AMPM 4855 S. HWY 99 Stockton <br /> UST SYSTEM RETROFIT OR REPAIR <br /> (Submit minimum of 3 sets of plans&applications as originals will be retained by EHD) <br /> 1. Site map enclosed? YES[) NO[] <br /> 2. Submit copies of ICC Service Technician and/or Installer's certificate and all manufacturer training certificates for each <br /> person installing or testing any component that is repaired or replaced. Ensure a copy of the'Site Health and Safety <br /> Plan'is available on the jobsite as required by Title B. <br /> 3. Detailed description of work to be completed. List components to be repaired or replaced and attach a diagram drawn <br /> to scale showing location of repairs and/or replacements. If repairing a component, describe how this will be done. (if <br /> adding piping, UDC's, or other UST equipment, or performing tank top upgrade, use the UST Installation Application <br /> pages 4-8 as necessary for a timely plan review): <br /> Replace 91 turbine relay <br /> Remove(2) Red Jacket CPT and pressure sensors on both 87 tanks. <br /> Replace CPT controllers with FE Petro Smart Controllers and Vaporless mechanical leak detectors. <br /> Pre-form Veeder-Root functionality test <br /> 4. List of equipment to be used(Attach manufacturer's specification sheets showing third-party approval): <br /> 1.Type H-Relay <br /> 2. FE Petro STP-SCI Single Phase Controller <br /> 2. Vaporless 99 LD2000 Mechanical Line Leak Detector <br /> nCZ 2 0 20 <br /> 3 <br />