Laserfiche WebLink
Site Preparatic R.nd Installation Manual V <br /> TLS-250i 'llll�lt Level Sensing System li <br /> IL SECTION 5. INTERSTITIAL LEAK CAUTION:DO NOT INSTALL THE SENSOR IF THERE IS ANY <br /> SENSOR INSTALLATION LIQUID IN TIIF. PIPING SUMP.FAILURE TO COMPLY <br /> CAN RESULT IN EQUIPMENT DAMAGE OR UNDE- <br /> A. RISER PIPE CAP PREPARATION.The riser pipe cap TE(-rED POTENTIAL ENVIRONMENTAL AND HEALTH <br /> must have a 1/2'-14N1'T tapped hole for passage of sensor HAZARDS. <br /> wires. Kits with pre-drilled caps are available from Veeder- 2. Make sure no liquid exists in the piping sump. <br /> Root.Order Kit No.312020-928,one for each sensor. <br /> 3. Position the piping swop sensor ata 46°angle from the <br /> Note: Kit No.312020-928 is for a standard 'L-inch riser. base of the sump to the sensor junction box (see Figure <br /> 12).Only the end of the sensurshould touch the bottom of <br /> B. INSTALLATION. Install each sensor as follows: the sump. <br /> WARNING: TO AVOID ELECTRICAL SHOCK WHICH <br /> COULD KILL YOU, BE SURE AC POWER TO THE <br /> MONITOR IS OFF DURING INSTALLATION. <br /> 1. Turn OFF power to the TIS-2501 system. <br /> CAUTION:DO NOT INSTALLTHE SENSOR IFANY LIQUID IS <br /> PRESENT IN THE ANNULAR SPACE. FAILURE TO <br /> COMPLY CAN RESULT IN EQUIPMENT DAMAGE OR <br /> UNDETECTED POTENTIAL ENVIRONMENTAL AND t;ripbtnw,',Idj <br /> HEALTH HAZARDS. ?-•% ieeL*S4�-"' .. .- <br /> LEADER CABLE LBylp9iBl! <br /> 2. Make sure no liquid is present in the annular space. ICCORD ORIR BEAL .p <br /> rmXE <br /> 3. To besure the sensor will reach the bol lennnf the annuhn <br /> space,First measure the sensor riser pipe from the bottom wI.O,C.,RL,„E <br /> ofthe pipe to the top.Then measure the panne distance up µBOA �� <br /> the leader cable from its connection to the Sensing <br /> element and mark the leader cable. <br /> CAUTION:DO NOT USE A KNIFE OR OTHER SHARP OIME.CT EPDXY SE"' "''EPER <br /> TO MARK THE CABLE; THIS MAY EXPOSE. THF. ^"E` <br /> WIRES. MARK THE DISTANCE WITH A MARKER, <br /> TAPE,OR A TWIST TIE. <br /> 4. Feed the sensor down the riser pipe until the point <br /> marked on the leader cable reaches the top or the riser <br /> pipe. Refer to Figures 2 and 3. <br /> 5. Feed the wire sensor cable up through the riser cap cable <br /> bushing and into the junction box through its cable <br /> bushing. <br /> 6. Tighten the cable bushing nuts on the riser cap all(] <br /> junction box to ensure a water-tight seal at the cable Figure 12. Piping Sump Sensor Installation Requirements <br /> entry. <br /> 7. Using wire nuts, connect the two-wire cable to the field <br /> wires in the sensor junction box.Be sure to observe color 4. Feed the leader cable through the cable bushing on the <br /> codes for proper polarity hookup to the TLS monitor. junction box. <br /> Refer to Figure 5, 'TI S-2501 Four-Tank System Wiring <br /> Installation Diagram." 5. Tighten the cable bushing nuts oil the riser cap and <br /> Note: DO NOT SEAL WIRE NUT CONNECTIONS AT THIS junction box to ensure a water-tight seal at the cable <br /> J TIME. Epoxy sealant, furnished with each sensor, entry. <br /> ! should only be installed after warranty checkout by 6. Using wire nuts, connect the two-wire cable to the field <br /> an authorized Veeder-Root TLS distributor. wires in the sensor junction box.Be sure to observe color <br /> S. Secure the riser cap to the riser pipe. codes for proper polarity hookup to the TLS monitor. <br /> Refer to Figure 5, 'TLS-250i Four-Tank System Wiring <br /> Installation Diagram" <br /> Note: DO NOT SEAL WIRE NUT CONNECTIONS AT THIS <br /> TIME. Epoxy sealant, furnished with each sensor, <br /> SECTION 6. PIPING SUMP should only be installed after warranty checkout by <br /> SENSOR INSTALLATION an authorized Veeder-Root TLS distributor. <br /> A. INSTALLATION. Install each piping sump sensor as 7. Tie the piping sump sensor to a point within the sump <br /> follows: <br /> where no condensation exists,to maintain the sensor's 45° <br /> angle. <br /> WARNING: TO AVOID ELECTRICAL SHOCK WHICH CAUTION: TIF. TIIE PIPING SUMP SENSOR TO A POINT <br /> COULD KILL YOU, BE SURE AC POWER TO THE WHERE. NO CONDENSATION WILL FORM. CONDEN- <br /> MONITOR IS OFF DURING INSTALLATION. SATION MAY CAUSE A CONSTANT WATER SENSOR <br /> L Turn OFF power to the TLS-2501 system. ALARM READING. <br /> 9 <br />