Laserfiche WebLink
Aris Cacapit, REHS <br /> San Joaquin County <br /> Environmental Health Department -2- October 3, 2012 <br /> 3. Page 6 section E of the Application for Underground Storage Tank Installation Permit does <br /> not have the box checked for Buoyancy Calculations. Check it. Submit corrected version. <br /> Response: The box for Buoyancy Calculations has been checked and the revised <br /> application included with this resubmittal. <br /> 4. Page 7 section G of the Application for Underground Storage Tank Installation Permit does <br /> not list the manufacturer and model of the overspill containment having minimum capacity of <br /> 5 gallons provided at each tank fill location. Fill in the blank. Submit corrected version. <br /> Response: The spill bucket information has been included on the revised application <br /> included with this resubmittal. The Manufacturer is: OPW and the Model No. is P511- <br /> EVRDV. <br /> 5. Page 7 section G of the Application for Underground Storage Tank Installation Permit lists an <br /> OPW 61fSTOP-2000 as the overfill prevention at 95%. However, an OPW61fSTOP is <br /> approved for aboveground storage tanks. Choose equipment that is approved for <br /> underground storage tanks. Correct the discrepancies. Submit corrected version. <br /> Response: Due to the fact that the underground fuel additive tank receives a pressurized <br /> delivery from the tanker truck, the only suitable full drop tube is the 61fSTOP-2000. Although <br /> typically used for ASTs, the function has been reviewed, revised and approved by <br /> Containment Solutions and OPW. See enclosed document "Pressurized Product Deliveries <br /> to CSI Underground Tanks" prepared by Containment Solutions dated May 12, 2011 is <br /> included in this resubmittal. <br /> 6. Page 7 section G of the Application for Underground Storage Tank Installation Permit <br /> indicates that an approved overfill prevention device must be provided at each tank fill <br /> location. Choose one of the following methods. You may refer to the State Water Resources <br /> Control Board Letter of Guidance 150-2. Submit corrected version. <br /> Response: This has been revised on the application included with this resubmittal. The <br /> Manufacturer is: OPW and the Model No. is P511-EVRDV. <br /> 7. Page 7 section H of the Application for Underground Storage Tank Installation Permit does <br /> not have checked Tie-downs, when used, constructed of non-corrosive material or coated <br /> steel. Check it. Submit corrected version. <br /> Response: This has been revised on the application included with this resubmittal. <br /> 8. Page 1 of the 8-9-12 monitoring plan in section 490-33 does not list the sump and sump <br /> interstitial sensors manufacturer and model numbers. Update it. Submit corrected version. <br /> Response: Page 1, Section 490-33 has been revised and is included with this resubmittal. <br /> The model numbers are: 794380-208 and 304. <br /> 9. Page 2 of the 8-9-12 monitoring plan in section 490-71 lacks the description of audible visual <br /> overfill alarm set @ 90% tank capacity. Update it. Submit corrected version. <br /> Response: The description has been revised. <br />