Laserfiche WebLink
Costco Gasoline#1091 2680 Reynolds Ranch Parkway Lodi, CA 95240 SR0065509 <br /> 7. Page 7 section H of the Application for Underground Storage Tank Installation Permit <br /> does not have checked Tie-downs, when used, constructed of non-corrosive material or <br /> coated steel. Check it. Submit corrected version. <br /> 8. Page 1 of the 8-9-12 monitoring plan in section 490-33 does not list the sump and sump <br /> interstitial sensors manufacturer and model numbers. Update it. Submit corrected <br /> version. <br /> 9. Page 2 of the 8-9-12 monitoring plan in section 490-71 lacks the description of audible <br /> visual overfill alarm set @ 90% tank capacity. Update it. Submit corrected version. <br /> 10. The site plan sheets list 322 East Harney Ln. It should list 2680 Reynolds Ranch Rd. <br /> Correct the discrepancies. Submit corrected version. <br /> 11. The site plan sheet T-2 of 12 Section A, B, D, and E have part numbers listed that do not <br /> match the part numbers listed on the parts list of site plan sheet T-4 of 12. Correct the <br /> discrepancies. Submit corrected version. <br /> 12. The site plan sheet T-3 of 12 Section E has part numbers listed that do not match the <br /> part numbers listed on the parts list of site plan sheet T-4 of 12. Correct the <br /> discrepancies. Submit corrected version. <br /> 13. The parts list on site plan sheet T-4 of 12 is incomplete. Page 8 section I of the <br /> Application for Underground Storage Tank Installation Permit lists Veeder-Root 794380- <br /> 208 as the sump sensor. Update the parts list on site plan sheet T-4 of 12 to include this <br /> sensor and any other parts to be installed. Submit updates with matching cut sheets. <br /> If you have any further questions, please contact me at (209) 468-3453. <br /> Thank you, <br /> Aris Cacapit, REHS <br /> Registered Environmental Health Specialist <br /> 2 <br />