Laserfiche WebLink
SWRCB,January 2002 Page_of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: x Took Manufacturer D Industry Standard 1.1 Professional Engineer <br /> 11 Other(Specify) <br /> Test Method Used: L1 Pressure x Vacuum U Hydrostatic <br /> 0 Other(Spec) <br /> Test Equipment Used: Dwyer Manometer Equipment Resolution:+1-20/a <br /> 2ok# Tank# Tank# <br /> , Tank# I TanI <br /> Is Tank Exempt From Testing?' 0 Yes xNo n Yes 11 No I'l Yes FI No 11 Yes ONo <br /> Tank Capacity: 10,000 <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Unknown <br /> Product 3tored: Diesel <br /> Wait firr c between applying <br /> pressure'vacuumtwater and 30 min 30 min 30 min 30 min <br /> siturting est: <br /> Test St a t Time: 11:30 <br /> initial R-ading(Rj): 7.23 <br /> Test Ent Time: 12:30 <br /> Final Roading(RO: 6.77 <br /> Test Duration: I hour I hour I hour I hour <br /> Change in Reading(RF-Rj): A6 <br /> Pass/Fail Threshold or Criteria: No less than I" No less than I" No less than I" No less than I" <br /> Test Result; x Pass 0 Fail 0 Pass 0 Fail 0 Pass a Fall 0 Pass 0 Fail <br /> Was sensor removed for testing? xYes LINO nNA xYes ONo DNA xYes LlNo DNA xYes LINo -.-;NA <br /> Was sensor properly replaced and xYes i xYes ONo DNA <br /> verified functional after testing? <br /> I <br /> Comm vats—(include information on repairs made prior to lesfing,and recommendedfollow-upforfailed rests) <br /> Secondary containment systems wbere the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code or Regulations,Title 23,Section 2637(a)(6)) <br />