Laserfiche WebLink
SWRCB January 2002 Page_of_ <br /> S. SECONDARY PIPE TESTING <br /> Test Me had Developed By: X Piping Manufacturer G Industry Standard 0 Professional Engineer <br /> n Other(Spec) <br /> Test Me had Used: X Pressure ❑Vacuum Cl Hydrostatic <br /> Other(Spec) <br /> Test Eq ipment Used: Pressure Gauge Equipment Resolution:0-15 PSI <br /> Piping Run N I Piping Run 112 Piping Run#3 Piping Run# <br /> Piping Material: Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Ameron Ameron Ameron <br /> Piping Diameter. 3" 3" 3" <br /> Length of Piping Run: 25' 20' 20' <br /> Product Stored: Diesel Diesel Sate Diesel Sate <br /> Method and location of Test boot Test hoot Test hont Test boot <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min 5 min 5 min <br /> starting test- <br /> Test S Time: 9:50 11:00 11:00 <br /> Initial Reading(Rj): 5 PSI 5 PSI 5 PSI <br /> Test End Time: 10:50 12:00 12:00 <br /> Final Reading(RF): 5 PSI 5 PSI 5 PSI <br /> Test Duration: I Haur I Hour I Hour I Hour <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass/Fail Threshold or 0 drop 0 drop 0 drop 0 drop <br /> Criteria: <br /> Test Result: x Pass ❑Fail x Pass ❑Fail x Pass D Fail G Pass D Fail <br /> Comments—(include itformation on repairs made prior to lesting, and recamnendedjallow-apjorjailed lusty) <br />