Page 2 of 8 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑ Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑ Pressure ©Vacuum ❑ Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank # 1 Tank # Tank # Tank # <br /> Is Tank Exempt From Testing?' ❑ Yes B No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Tank Capacity: 4000 <br /> Tank Material: FG <br /> Tank Manufacturer: UK <br /> Product Stored: Diesel <br /> Wait time between applying <br /> pressurelvacuumlwater and starting 5 m i n <br /> test: <br /> Test Start Time: 12:30 <br /> Initial Reading(Ri): -10" <br /> Test End Time: 1:30 <br /> Final Reading(RF): -10" <br /> Test Duration: 1 h r <br /> Change in Reading(RF-Ri): 0 <br /> PasslFail Threshold or Criteria: 0 <br /> Test Result: a Pass ❑ Fail ❑ Pass ❑ Fall ❑ Pass © Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? 0 Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> Was sensor properly replaced after 0 Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> testing? <br /> Comments--(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, <br /> such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. <br /> {California Code of Regulations, Title 23,Section 2637(a)(6)) <br />