Laserfiche WebLink
B.5) The main fitting body (Item A) should be installed to Interstitial Test Port <br /> the outside first. Then apply adhesive as shown (Fig. 65). (Only on Flange) <br /> 0 K1, + Adhesive <br /> 1 � � Injection <br /> The Adhesive Injection Port on the fitting body Port <br /> must be at the 12-o-Clock or North Position. I f <br /> i <br /> The Interstitial Test Port on the Flange <br /> must be at 12-o-Clock or North Position. (Fig.' X) <br /> Fig. 135 Fig. B8 <br /> Adhesive Fill <br /> Bead <br /> Here <br /> 360° <br /> Item B <br /> Item A (Flange) <br /> (Main body) <br /> / <br /> Adhesiver// I <br /> OUTSIDE / <br /> Install Main body to outside of sump Install the loose Flange <br /> and apply adhesive to areas shown and use gloved finger to run a <br /> generous bead along joint. <br /> 6.6) Apply adhesive to the Main Body's outer surface 3600 where shown. Fig. B7 <br /> After applying adhesive to all contact areas (Fig. 65)Apply the flange over <br /> the fitting and to the wall (Item B, Fig. B.5) <br /> 6.7) Apply the Bravo Clamp immediately as shown in Fig. B7. Install clamp <br /> shown to the body roughly 1/4"from the face and tighten.Then hand-tighten <br /> each bolt so it is snug.Apply a 1/4- 1/2 tum to each bolt evenly until the <br /> clamp starts to slide away from the wall and flush with the face of the fitting. CLAMP <br /> 6.8) Apply a generous bead of adhesive as shown. (Fig. 138). INSIDE <br /> B.9) Glue all penetration fittings and allow to cure following the <br /> pipe manufacturers adhesive instructions. <br /> 7 ii-F-Series-lX-SS-D-11A <br />