Laserfiche WebLink
ICONF I I]ENC,-,e tJST E3 ER V I CES,,,y I NC - <br />417 MMNTCLAXR OI REST BGiKERBFIHl..O. CM 9aamD <awn6 6a1-aa70 <br />RES/System II Precision leak Test Graph (OverFill) <br />Invoice No.g 1920 Dateg 06/07/95 Time a 08:44:00 <br />Tank Diameter(in): 95 <br />Technician: DMY Tank: i product Level(in)g 131 <br />Volume(gal): 5000 Grade Level(in)g 1.42 <br />Water Level On Tank(in): 0 <br />Coefficient Of Expansions 0.0006609 <br />Specific Gravitya .75 <br />Calibration Value(ml): 200 Channels 1 <br />Level Segment Froma 60 To 290 Temp Segment From: 60 To 290 <br />1M <br />T is <br />E <br />I Cj <br />P :. . <br />Change In Calibration Zone = 27 <br />Starting Temperature (F)a 71.906 <br />Surface Rrea(sq. in)g 45.2 <br />Level volume(gph)a -0.17 <br />Temp. volume(gph)a -0.14 <br />Net change(gph) -0.03 <br />Rea ss t -t 1 t --> PASS <br />Copyright (c) 1989 by RES, Inc. <br />** Notes ** <br />Calibration Unit(gal/unit) = 0.00196 <br />Head Pressure(psi (Btm))a 3.55 <br />Temp. Change(F/h) a -0.044 <br />Product Line(gph)a -0.003 <br />i:N/L --> F'Ass <br />TERESI TRUCKING , 900 1/2 VICTOR ROAD , LODI, CA. <br />THIS IS A HIGH LEVEL TEST WITH A 200 ML. CALIBRATION. <br />w <br />