Laserfiche WebLink
CONF= I DF=NOftr- UST SE R V I CF='L. * I NC - <br />�.17 MCJNTCL_RIR MTRMF_ HRKF_RnrIM_ 0' CR 933mv C006) A31-3070 <br />AES/System II Precision leak Test Graph (OverFill) <br />Invoice No.: 1920 <br />Dates <br />Technicians DMY <br />Tanks <br />Volume(gal): 12000 <br />Grade <br />Water Level On Tank(in): <br />0 <br />Specific Gravity: .87 <br />Calibration Value(ml): <br />200 <br />Level Segment Froms 1 <br />To 275 <br />X111 <br />L <br />V <br />E. <br />0 <br />T ri <br />E <br />06/27/95 Time s 08:44:00 <br />2 Tank Diameter(in)s 95 <br />Level(in)s 144 Product Level(in)s 142 <br />Change In Calibration Zone a 55 <br />Starting Temperature (F)s 68.357 <br />Surface Area(sq. in): 19.1 <br />Level volume(gph)s <br />Temp. volume(gph)s <br />Net change(gph) s <br />Result --> <br />Copyright (c) 1989 <br />** Notes ** <br />-0.07 <br />-0.05 <br />-0.02 <br />aaaaaaaasa <br />F=NASS <br />by RES, Inc. <br />Coefficient Of Expansions 0.0004463 <br />Channels 3 <br />Temp Segment Froms 1 To 275 <br />F) <br />Calibration Unit(gal/unit) a 0.00096 <br />Head Pressure(psi (Btm)): 4.46 <br />Temp. Change(F/h) : -0.011 <br />Product Line(gph)s SUCTION <br />F=1lL --> <br />TERESI TRUCKING , 900 1/2 VICTOR ROAD , LODI, CA. <br />THIS IS A HIGH LEVEL TEST WITH A 200 ML. CALIBRATION. <br />THE PRODUCT LINE IS FLOODED AND INCLUDED IN THESE DATA. <br />P A S E3 <br />