Laserfiche WebLink
SWRCB,January 2002 Page 2 of 8 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: U Tank Manufacturer N Industry Standard U Professional Engineer <br /> U Other(Spec) <br /> Test Method Used: U Pressure E Vacuum U Hydrostatic <br /> U Other(Specify) <br /> Test Equipment Used: Vacuum Generator/Ga es Equipment Resolution: <br /> Taok# 1 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' U Yes N No U Yes U No U Yes U No U Yes U No <br /> Tank Capacity: 1000/1000 <br /> Tank Material: Class Clad S 1 <br /> Tank Manufacturer: o <br /> Product Stored: Re /Plus <br /> Wait time between applying <br /> pressure/vacuum/waterand hr <br /> starting test: <br /> Test Start Time: 10:45 <br /> Initial Reading(R,): 7" HG <br /> Test End Time: 11 •4 5 <br /> Final Reading(RF): 7" •HG <br /> Test Duration: 1 hr, <br /> Change in Reading(R,-R,): 0 <br /> Pass/Fail Threshold or Criteria: n Loss <br /> Test Result: Xl Pass U Fail U Pass U Fall U Pass U Fall U Pass U Fall <br /> Was sensor removed for testing? Ig Yes U No U NA U Yes U No U NA U Yes U No U NA U Yes U No U NA <br /> Was sensor properly replaced and IIYes U No UNA U Yes U No U NA U Yes U No UNA1 U Yes U No U NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommended follow-up forfailed tests) <br /> 'Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br />