Laserfiche WebLink
SWRCB,January 2002 JUN 2 9 2015 Page_of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: Sump Manufacturer 111duWfessional Engineer <br /> (Specify) ,jr_O,,T's OTSncMT <br /> Other <br /> I est Method Used: Pressure Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Cscd: Caldwell Lcvcl Change Indicator Vquipment Resolution: .002 <br /> Sump# 1-87 Sump#2-91 Sump# Sump# <br /> Sump Diameter: 42" 42" <br /> Sump Depth: 45" 44" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 22' 22" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 12" 12" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' Water Line 24" Water Line 24" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both Yes Yes <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe Yes Yes <br /> shutdown?* <br /> Was fail-safe verified to be No No <br /> operational?* <br /> Wait time between applying water 10 Minutes 10 Minutes <br /> and starting test: <br /> Test Start Time: 9:15 10:05 <br /> Initial Reading(R,): .001 .001 <br /> Test End Time: 9:45 10:35 <br /> Final Reading(RF): .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing and recommended follow-up forfailed tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />