Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />May 04, 2018 <br /> Facility Address: <br /> 2115 W YOSEMITE AVE, MANTECA <br /> Facility Name: <br /> 7 ELEVEN 2369-39858A <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 111 CCR 2638(a) Failed to test monitoring and leak detection equipment annually. <br />Annual monitoring system certification and leak detector testing were last performed on 03/29/2018 and was due <br />next calender year. Monitoring system certification testing is being performed on 05/04/18, and is two months past <br />due. These tests are required once every 12 months. Take all necessary precautions to ensure testing is <br />performed in a timely manner. <br />This is a repeat violation, Class II. <br /> 115 CCR 2715(a) Failed to submit to EHD notification of designated operator identification or change w/in 30 days. <br />A new designated operator was chosen since the last monitoring certification and notification was not provided to <br />the EHD within 30 days of the change. ECO-Check is the designated operator. The current Designated operator <br />form on CERS indicates Afforda-test as the DO Any changes shall be reported to the EHD within 30 days. <br />Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov and upload <br />the notification identifying all the designated operators for this facility. <br />This is a minor violation. <br /> 201 CCR 2712(b) Failure to maintain monitoring, maintenance, and follow up action records. <br />The facility, and the designated operator failed to check that alarms were responded to appropriately. The missing <br />alarms include an L23 Dispenser 1-2 brine alarm that occurred on the designated operator monthly inspection <br />reports dated: 2/15/18, 1/18/18, 12/21/17, 11/17/17, and 10/27/17. During the monthly inspection, the designated <br />operator shall review the alarm history for the previous month, check that each alarm was documented and <br />responded to appropriately, and attach a copy of the alarm history with documentation taken in response to any <br />alarms to the monthly report. Ensure that designated operators performing monthly inspections at this facility are <br />including all of the required information on the reports. <br />This is a minor violation. <br /> 209 CCR 2715(c) Designated operator did not inspect all required items and/or the inspection reports not completed. <br />The designated operator failed to check and note the correct test dates for the last monitoring system certification <br />that occurred on 3/29/17 on the April 2017 through April 2018 designated operator monthly inspection reports. <br />During the monthly inspection, the designated operator shall check that all required testing and maintenance for the <br />UST system have been completed and document the dates they were done. Ensure that designated operators <br />performing monthly inspections at this facility are including all of the required information on the reports. <br />This is a minor violation. <br />Page 4 of 5 <br />FA0017819 PR0526335 SC001 05/04/2018 <br />EHD 23-01 Rev. 10/31/2017 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com