SWRCB,January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: Sump Manufacturer Industry Standard X Professional Engineer <br /> Other(.Speci ) <br /> Test Method Used: Pressure Vacuum X Hydrostatic <br /> Other(Spec�j <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> Sump# 1-87 Sump#2-91 Sump#3-Diesel Sump# <br /> Sump Diameter: 44" 44" 44" <br /> Sump Depth: 39" <br /> 39" 37 Y.., --... <br /> Sump Material: Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of <br /> -Highest Piping Penetration: 19 18" 12" <br /> Height from Tank Top to Lowest <br /> ElectricalPenetration: I I' 23" 22" <br /> Condition of sump prior to testing: Dry Dry Dry <br /> Portion of Sump TestedWater Line 25" Water Line 27" Water Line 26" <br /> Does turbine shut down when <br /> ,sump sensor detects liquid(both Yes Yes Yes <br /> product and water)?' <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe <br /> shutdown?' Yes Yes Yes <br /> Was fail-safe verified to be <br /> operational?' No No No <br /> Wait time between applying water <br /> and starting test: 5 Minutes 5 Minutes 5 Minutes <br /> Test Start Time: 10:52 10:07 9:22 <br /> Initial Reading(Ri): .001 .001 .001 <br /> Test End Time: 11:22 10:37 9:52 <br /> Final Reading(RF): .001 .001 <br /> .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? Yes Ve9 Yes <br /> Was sensor properly replaced and <br /> verified functional after testing? Yes Yes Yes <br /> Comments—(include information on repairs made prior to resting and recommended ollow up%r piled tests) <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to an of the questions indicated with an <br /> asterisk * 1 <br /> O is"NO"or"NA",the entire sump must be tested. (See S W RCB LG-160) <br />