Laserfiche WebLink
12/06/2013 12:00 209367542 BAGLEY ENT C— PAGE 01/01 <br /> ■ e`?''�I". • San Joaquin County <br /> BVED <br /> A P4 <br /> Environmental Health Department wa 5 rs dal_ <br /> 1868 E.Hazelton five,-Stockton,(A 95245 DEC 10 2013 <br /> I Joaquin County f w� t °�,d yv�e, <br /> Ujps � MdC��� C-1 <br /> ARIS CACAPIT REHS MBA ntal Health Dep MEf� °R '` <br /> Heran, REHS IZlt'll 3.. <br /> Senior Registered Environmental Health Specialist �ast Hazelton Avenue LTM OEPARTME { <br /> n, California 95205-6232 PROGRAM COORDINATORS <br /> Rcbert McClellon, REHS <br /> Email-acacapit0)sjcehd.com (209)46F-3453 -- - ---- -- Jeff CarruAsco.REHS, RFD1 <br /> EHD Website:http://www.sjgov.Drg/chd Fax(209)468-3433 site: www.sjgov.org/ehd Kaley Fnley, REHS <br /> Linda Mirk-Atte.REHS <br /> — alone: (209) 468-3420 Rodney Estrada. REHS <br /> Fax: (209) 4640138 Adrienne Ellsaesscr. REHS <br /> November 27, 2013 <br /> Joseph Bagley <br /> 2370 Maggio Circle#4 '� � � <br /> Lodi, CA 95240 <br /> 95 42 <br /> Re: Lodi Muni Service Center 1331 S. Ham Ln, Lodi, CA 242 SR 68175 <br /> The San Joaquin County Environmental Health 17epartment (EHD) has completed the review of <br /> the application for a permit to remove and replace the 87 overfill alarm and remove and replace <br /> the 87 T2 fill bucket drain valve on the underground storage tank (UST) system at the above <br /> noted address. The permit has been approved with the following conditions: <br /> 1. Contact the local fire department and the San Joaquin Valley Air Pollution Control <br /> District for any applicable permits and requirements. <br /> 2. Any changes in information and scope of work must be submitted to EHD for approval <br /> prior to commencing work. All new addenda supersede the previous ones. <br /> 3. Contact Aris Cacapit at (209) 468-3453 to arrange the following inspection appointments <br /> (a 48-hour notice is required for inspection appointments). Please be aware that <br /> inspections for emergency work must be scheduled within five days of permit approval. <br /> a, Sensor functionality: Functionality of the monitoring system must be verified to <br /> ensure that monitoring has been restored to meet the requirements of Title 23 <br /> California Code of Regulations and the Health & Safety Code. If it is determined that <br /> a cold start is necessary, a copy of the alarm history shall be printed prior to <br /> performing the "cold start" of the Veeder Root system and made available at the time <br /> of EHD inspection. <br /> b. Overfill prevention verification: Verify that external audio and visual alarm activates <br /> when tank is 90% full_ <br /> c. Spill bucket test: Verify minimum 5-gallon capacity and pass a one hour hydrostatic <br /> test (or equivalent). Proper drainage must also be verified. <br /> Please be aware that the facility cannot receive fuel in the 87 T2 tank prior to the <br /> EHD inspection and approval. <br /> 4. Qualified service technicians must possess or work under the direct and personal <br /> supervision of an individual physically present at the work site who possesses all of the <br /> following: <br /> a. One of several permissible valid, current contractor's licenses issued by the <br /> Contractors State License Board (may be issued to the installation company), or a <br /> Tank Tester's license issued to the individual by the State Water Board, and <br /> Received Time Dec. 6. 2013 11 : 04AM No. 4705 <br />